TM0064
Page 50 of 91
Issue 2.01
The description displayed for types of devices, i.e. BREAK GLASS, are listed in the appropriate
Device Manual.
The capital letters denote the following:
D
-
Loop/Device
Z
-
Zone
A
-
Analogue value
F
-
Fire threshold
I
-
Isolated
If a device is isolated this will be indicated on the display be a capital I on the bottom line of the
display, extreme right hand character.
When the listing is completed the panel will automatically revert to the option one, menu one
display mode. To list a further loop the option must be re-selected and the required loop number
entered.
3.2.4 List Isolated Devices
Selecting this option will take you directly into the listing of isolated devices. If the printer is
enabled the listing will also be hard copied. The listing can be aborted using the CANCEL/NO
key. A typical display is shown in fig 3.2.17.
ASSEMBLY WORKSHOPS
ZONE 12 IONISATION DEVICE 067 LOOP 02
Fig 3.2.17
If no devices are isolated then the NO DEVICES ISOLATED message is displayed for a few
seconds before the panel returns to displaying the first option of menu two.
The listing to the printer is a direct copy of the LCD/VFD.
3.2.5 Select Test Mode
This allows fire testing to be performed on the system without the standard sounders being
operated. Loop devices operated by the site programming will be activated. Either a loop or
zone can be tested. This allows an area to be fire tested but at the same time if a fire call comes
from an area not being testing it will override the test and perform as a normal fire alarm.
TUE 15 MAR 21:45 SELECT TEST MODE
LOOP?
Fig 3.2.18