TM0064
Page 60 of 91
Issue 2.01
Enter file name
PanelB
Fig 3.3.24
Please note that when files are saved to C pack on the Psion a considerable wait time is involved
if a datapack is used. During this period the Psion will indicate that it is copying a file.
3.3.6 Isolate AUX Outputs
This option allows the isolation of the Auxillary outputs.
Select the option by scrolling the display using the CANCEL/NO key until this option is
displayed on the LCD/VFD, once displayed press the ENTER/YES key to accept.
The LCD/VFD will display a request to either ISOLATE or DE-ISOLATE as per figs 3.3.25 and
3.3.26 respectively.
To isolate/de-isolate press the ENTER/YES key. If the CANCEL/NO key is pressed the display
will exit this option, and the status of the Auxiliary output left unchanged.
The panel will indicate EXTERNAL FAULT when AUXILIARY isolated.
TUE 15 MAR 21:45 ISOLATE AUX. OUTPUTS
ISOLATE AUX O/Ps?
Fig 3.3.25
TUE 15 MAR 21:45 ISOLATE AUX. OUTPUTS
DE-ISOLATE AUX O/Ps?
Fig 3.3.26
3.3.7 Change Baud Rate
There are two baud rates: 300 and 2400: Each time the enter key is pressed the baud will toggle
between 300 baud and 2400 baud.
TUE 15 MAR 21:45 CHANGE BAUDRATE
LOAD/SAVE BAUDRATE 2400
Fig 3.3.27