4.
From the Keyscan NETCOM Utility screen, select the Program CA150 Rev. B Device button.
5.
From the CA150 Rev. B Program Settings screen, enter the IP address assigned to the CA8WL-AL’s on-
board Ethernet module in the IP Address to Assign field. If using DHCP, enter 0.0.0.0 in the IP Address
field.
6.
If a subnet mask is required, select it from the drop down list.
7.
If the CA8WL-AL’s on-board Ethernet module requires a gateway to communicate on the network, enter
the gateway in the Default Gateway field; otherwise by-pass this step.
8.
Click on the down arrow below and to the right of Program via IP Address or Serial Port. From the drop
down list, select the laptop/PC port connected with the data serial cable.
9.
Click on the down arrow below and to the right of Communications Baud Rate and select the same baud
rate that corresponds to the S1.2 DIP switch setting on the CA8WL-AL control unit.
10.
Leave Ethernet Connection Type set on Automatic Negotiation unless the IT administrator gives a specific
setting.
If the NETCOM device experiences network communication difficulties, you may have to alter the
Ethernet Connection Type from automatic negotiation. (The Ethernet Connection Type is the network
speed & duplex setting). Set the NETCOM so it matches the network equipment setting. If the
network equipment was on an automatic setting, then reconfigure both the network equipment, which
may include routers or switches, and the NETCOM to a matching fixed speed and duplex setting. As
an example, NETCOM = 100 Mbit/Half Duplex – Network equipment = 100Mbit/Half Duplex.