Keyscan Inc. A Member of the Kaba Group – CA8WL-AL Rev. B Installation Guide (07.15)
35
6.
Select start > All Programs > Keyscan NETCOM Program Tool and select Keyscan NETCOM Program Tool.
7.
From the Keyscan NETCOM Utility screen, select the Program CA150 Rev. B Device button.
8.
From the CA150 Rev. B Program Settings screen, enter the IP address assigned to the CA8WL-AL’s on-
board Ethernet module in the IP Address to Assign field.
9.
Click on the down arrow below and to the right of Subnet Mask and select the subnet mask from the drop
down list.
10.
If assigned, enter the gateway in the Default Gateway field; otherwise by-pass this step.
11.
Click on the down arrow below and to the right of Program via Port. From the drop down list, select the
laptop/PC COM port with the data serial cable connection to the CA8WL-AL.
12.
Click on the down arrow below and to the right of Communications Baud Rate and select the same baud
rate that corresponds to the S1.2 DIP switch setting on the CA8WL-AL control unit.
13.
Leave Ethernet Connection Type set on Automatic Negotiation unless the IT administrator gives a specific
setting.
If the CA8WL-AL’s on-board Ethernet module experiences network communication difficulties, you
may have to alter the Ethernet Connection Type from automatic negotiation. (The Ethernet
Connection Type is the network speed & duplex setting). Set the CA8WL-AL baud rate so it matches
the network equipment setting. If the network equipment was on an automatic setting, then
reconfigure both the network equipment, which may include routers or switches, and the CA8WL-AL
Rev. B to a matching fixed speed and duplex setting. As an example, CA8WL-AL = 100 Mbit/Half
Duplex – Network equipment = 100Mbit/Half Duplex.