29
6.7 Number of extinctions before cleaning
– this parameter is available only when
the cleaning mechanism operates in AUTO mode or COMBI and determines which
in turn goes off to start the procedure of cleaning.
6.8 Minimum operating time without cleaning
– this parameter is available only
when the cleaning mechanism operates in AUTO or COMBI mode. Specifies the mi-
nimum number of hours the burner must in order to start cleaning. If the minimum ti-
me is not reached, the cleaning will not run even if there was a required number of
shut downs. Setting the parameter to „0h" control the minimum time off work without
cleaning.
6.9 The maximum working time without cleaning
– this parameter is available on-
ly when the cleaning mechanism operates in AUTO or COMBI mode. Specifies how
many hours the burner can work without cleaning. If the maximum time is reached,
the cleaning will run even if there was no required number of shut downs.
7.x Central heating pump work parameters.
7.1 Central heating pump switching on parameters
– this parameter specifies the
method of central heating pump switching on. Selection of „THERMOSTAT” setting
means that central heating pump will be switched on only if room thermostat con-
tacts are closed and in case of emergency (e.g. boiler overheating). Selection of
„AUTO” setting means that central heating pump operation will follow regardless of
room thermostat.
7.2 Periodic switching pump
– this parameter allows you to run the function
periodic heating pump to move water in the heating circuit. The pump is activated for
30 seconds at intervals set in the parameter TIME PERIOD. ON. PUMP CO. This
function is available when the CO pump mode is set to the value of TERM.