Press the MENU button
for 1 second to display the
parameter in order to save
the modified value, or MENU
quickly to quit the function
without saving.
Press the + and – buttons to
scroll through the functions to
modify other parameters.
Press the MENU button quickly
to quit the menu.
PARAMETERS
DESCRIPTION
DEFAULT
MIN
MAX
UNIT
1
TCL
Automatic reclosure time (0 = off)
0
0
900
s
2
ttr
Reclosing time after transit on PH1
(0 = off)
0
0
30
s
3
SEI
Sensitivity on obstacles
0 = Maximum impact force
10 = Minimum impact force
3
0
10
4
SFO
Motor speed during opening
1 = minimum
2 = low
3 = medium
4 = high
5 = maximum
4
1
5
5
SSO
Motor speed during opening deceleration phase
1 = minimum *
2 = low *
3 = medium
4 = high
5 = maximum
1
1
5
6
SFC
Motor speed during closing
1 = minimum
2 = low
3 = medium
4 = high
5 = maximum
4
1
5
7
SSC
Motor speed during closing deceleration phase
1 = minimum *
2 = low *
3 = medium
4 = high
5 = maximum
1
1
5
8
SBS
STEP BY STEP or SBS configuration:
0 = Normal (AP-ST-CH-ST-AP-ST…)
1 = Alternate STOP (AP-ST-CH-AP-ST-CH…)
2 = Alternate (AP-CH-AP-CH…)
3 = Apartment block – timer
4 = Apartment block with immediate reclosure
0 ***
0
4
9
sT2
Additional stop input:
0 = disabled
1 = The PAR input becomes the STOP function. NO
contact input
0
0
1
10
LSI
Deceleration distance
0 to 100 = Motor deceleration percentage during
opening and closure
20
0 **
100
%
11
BlT
Post blackout procedure
0 = No action, remains stationery
1 = Closure
0
0
1
s
12
SBY
Energy saving: enables photocell switch-off when
gate is closed
0= disabled
1= enabled
0
0
1
* = only for SUN4224/SC4224
** = for SUN4224/SC4224 min 15
*** = The default value for barriers is 4