3.2
Details of the additional soft start/soft stop module
(IL-3RW40)
Maximum power (kW)
at switching output
6.5 kW
Nominal current range
2 x 12.5 A
Weight
3.5 kg
Dimensions (LxWxD)
378 x 188 x 180 mm
Operating voltage
400 V / 50Hz
Working temperature
0 - 40°C
Protection rating
IP 54
Protection class
I
Connection type
Direct connection
to main control unit
The control unit must be operated outside the potentially
explosive area. Please note and follow the enclosed operat-
ing instructions for the soft start/soft stop.
3.3
Details of the additional frequency inverter module
(IL-Frequency)
Maximum power (kW)
at switching output
4 kW
Nominal current range
2 x 9.5 A
Weight
22 kg
Dimensions (LxWxD)
500 x 500 x 210 mm
Operating voltage
400 V / 50Hz
Working temperature
0 - 40°C
Protection rating
IP 54
Protection class
I
Connection type
Direct connection
to main control unit
The control unit must be operated outside the potentially
explosive area. Please note and follow the enclosed operat-
ing instructions for the soft start/soft stop.
WARNING
Temperature class
Temperature class T3 (maximum surface temperature of
200°C) applies to motors operated via frequency control
"Conditions for use of frequency inverters"
EN
010-532_02_SON
Installation and operating instructions
51 / 124
Summary of Contents for Aqualift Comfort 400V Duo