SUPERtrol II Flow Computer
67
6.9
OTHER
INPUT
(Continued)
OTHER INPUT
Set the low scale value for the analog current input signal (value for
0 or 4 mA input current). The value entered here must be identical to
the value set in the pressure, temperature or density transmitter.
Input:
Number with fixed decimal point: -9999.99...+9999.99
Display:
32.00 of
LOW SCALE VALUE
Set the full scale value for the analog current input signal (value for
20 mA input current). The value entered here must be identical to the
value set in the pressure, temperature or density transmitter.
Input:
Number with fixed decimal point: -9999.99...+9999.99
Display:
752.00 of
FULL SCALE VALUE
A fixed value can be defined for the assigned variable (pressure,
temperature, density). The flow computer will use this value in the
following cases:
• In case of error (i.e. defective sensors). The flow computer
will continue to operate using the value entered here.
• if "MANUAL TEMPERATURE", "MANUAL PRESSURE" or
"MANUAL DENSITY" was selected for "INPUT SIGNAL".
Input:
Number with fixed decimal point: -9999.99...+9999.99
Display:
70.00 of
DEFAULT VALUE
Define the STP reference conditions (standard temperature and
pressure) for the variable assigned to the input. Presently, standard
conditions are defined differently depending on the country and
application.
Input:
Number with fixed decimal point:
-9999.99...+9999.99
Display:
60.00 of
STP REFERENCE
LOW SCALE VALUE
FULL SCALE VALUE
DEFAULT VALUE
STP REFERENCE