SUPERtrol II Flow Computer
58
FLOW INPUT
6.8
FLOW INPUT
(Continued)
Enter the geometric ratio for the square law device being used. This
value is given by the manufacturer of the orifice plate, or other square
law device.
Note:
"Beta" is only required for measuring gas or steam with some
square law flowmeters.
Input:
Number with fixed decimal point: 0.0000...1.0000
Display:
1.0000
ENTER BETA
ENTER BETA
CAL. DENSITY
Enter the calibration density. This is the fluid density upon which the
flowmeter's calibration is based.
Input:
Number with floating decimal point in requested units:
0.000...10.000
Display:
8.3372 (#/gal)
CAL. DENSITY
Enter the K-Factor of the flowmeter.
Note:
• The K-Factor is expressed in pulses per unit volume (as
defined by "total units")
Input:
Number with floating decimal point: 0.001...999999
Display:
.000 ft3/h
LOW FLOW CUTOFF
Enter the inlet pipe diameter or bore for the piping section upstream
of the flow measurement device.
Input:
Number with floating decimal point: 0.001...1000.00
Display:
4.090 in
INLET PIPE BORE
K-FACTOR
INLET PIPE BORE