6
PROCESS VALUE STABILIZATION
(1, SCALE HIGH POINT)Unit
It is used for controlling if process value oscillates or not
when Parameter is or If;
condition is not true, then device start tunn operation
- <= Process Value <= +
SCALE LOW POINT :
SCALE HIGH POINT :
Minimum process input value in Pt-100
and Tc inputs. -1999 for fixed dual point display adjustment
used inputs, Scale low point is the lowest one from
or
for selectable dual point display adjustment used inputs
lowest
display adjustment
Maximum process input value in Pt-100
and Tc inputs. 9999 for fixed dual point display adjustment used
inputs, Scale high point is the biggest one from
or
for selectable dual point display adjustment used inputs
display adjustment
Scale low point is the
one from
or
for multi
point
used inputs
Scale high point is the biggest one from
or
for
multi point
used inputs
PROPORTIONAL BAND SHIFTING
((- SCALE HIGH POINT / 2 ) , ( SCALE HIGH POINT / 2 ) )Unit
SENSOR BREAK OUTPUT VALUE
(FOR HEATING PID 0.0, 100.0)%
(FOR COOLING PID -100.0, 0.0)%
If cooling function is performed ;
Cooling process set value is calculated by adding set value
With parameter
Control form can be ON/OFF or PID.
If set value for heating = +
;
Then set value for cooling = + +
When sensor breaks, controlling of the process can continue
by entering %output value to
parameter.
If this parameter 0.0, process control output does not perform
an output when sensor breaks.
ýoP1 ConF:MODULE-1 Configuration Parameters
These
devices are equipped with a 0/4 to 20 mA analog
i
input plugged into Module-1
Configuration
o
f
analog
input
module
in
Module-1socket.
TC
input
type
selection.
This
must
be
selected
if
analog
input
module
in
Module-1
socket
is
EMI-430.
PT-100
input
type
selection.
This
must
be
selected,
if
analog
input
module
in
Module-1
socket
is
EMI-440.
Z
Voltage / Current input type selection.
This must be
selected
since
analog input module
is
in Module-1 socket
.
Input Module Selection
MOD
U
L
E
-1
Z
Z
Voltage/Current
Voltage/Current
It is active if input type of Module-1 is selected
0...50mV
Z
( -1999 ; 9999 )
0...5V
Z
( -1999 ; 9999 )
0...10V
Z
( -1999 ; 9999 )
0...20mA
Z
( -1999 ; 9999 )
4...20mA
Z
( -1999 ; 9999 )
point position for display
.
It is active if input type of Module-1 is selected
Z
Voltage /Current.
No point
000.0
00.00
0.000
Calibration type
.
It is active if input type of Module-1 is selected
Z
Voltage /Current.
Fixed dual point calibration is performed. Minimum
value of calibration is -1999 and maximum value of
calibration is 9999.
Selectable dual point calibration is performed.
Defines minimum value for selectable dual point calibration.
.
It is active if input type of Module-1 is selected
Z
Voltage /Current.
Defines maximum value for selectable dual point calibration.
.
It is active if input type of Module-1 is selected
Z
Voltage /Current.
Unit selection
Unit is
°C
Unit is
°F
Unit is U
.
No unit.
Minimum value of operating scale (Low Limit). It can be
changed according to analog input type and scale.
Maximum value of operating scale (High Limit). It can be
changed according to analog input type and scale
Display offset for value in analog input module. It can be
adjusted from -10% to +10% of scale.
This value is added
to
the process value.
It is filter time for input signal. It can be adjusted from 0.0
to
900.0
It determines if the measured value from analog input module
in
Module-1 socket is used as Remote Set or not.
This parameter
is
visible if point position and unit parameters are same for
process
input and analogue input module.
Measured value from analogue input module in Module-1
socket is used as process set value. User defined process
set value is not considered
Measured value from analogue input module in Module-1
socket is not used as process set value. User defined
process set value is considered