PROCESS VALUE STABILIZATION

(1, SCALE HIGH POINT)Unit

It is used for controlling if process value oscillates or not

when           Parameter is             or             If;

condition is not true, then device start tunn operation

-            <= Process Value <=            +

SCALE LOW POINT :

SCALE HIGH POINT :

Minimum process input value in Pt-100

and Tc inputs. -1999 for fixed dual point display adjustment

used inputs, Scale low point is the lowest one from

or

for selectable dual point display adjustment used inputs

lowest

display adjustment

Maximum process input value in Pt-100

and Tc inputs. 9999 for fixed dual point display adjustment used

inputs, Scale high point is the biggest one from

or

for selectable dual point display adjustment used inputs

display adjustment

Scale low point is the

one from

or

for multi

point

used inputs

Scale high point is the biggest one from

or

for

multi point

used inputs

PROPORTIONAL BAND SHIFTING

((- SCALE HIGH POINT / 2 ) , ( SCALE HIGH POINT / 2 ) )Unit

SENSOR BREAK OUTPUT VALUE

(FOR HEATING PID 0.0, 100.0)%

(FOR COOLING PID -100.0, 0.0)%

If cooling function is performed ;

Cooling process set value is calculated by adding set value

With parameter

Control form can be ON/OFF or PID.

If set value for heating  =             +

;

Then set value for cooling  =             +            +

When sensor breaks, controlling of the process can continue

by entering %output value to

parameter.

If this parameter 0.0, process control output does not perform

an output when sensor breaks.

ýoP1 ConF:MODULE-1 Configuration Parameters

These 

devices are equipped with a 0/4 to 20 mA analog 

i

 

input plugged into Module-1

Configuration

 

o

analog

 

input

 

module

 

in

 

Module-1socket.

TC

 

input

 

type

 

selection.

 

This

 

must

 

be

 

selected

 

if

 

analog

 

input

 

module

 in 

Module-1

 

socket

 

is

 

EMI-430.

PT-100

 

input

 

type

 

selection.

 

This

 

must

 

be

 

selected,

 

if

 

analog

 

input

 

module

 

in

 

Module-1

 

socket

 

is

 

EMI-440.

Z

 

Voltage / Current input type selection.

 

This must be

 

selected 

since

 analog input module 

is 

in Module-1 socket

.

Input Module Selection

MOD

U

L

E

-1

 

Z

Z

Voltage/Current

Voltage/Current

It is active if input type of Module-1 is selected

0...50mV

Z

( -1999  ; 9999 )

0...5V

Z

( -1999  ; 9999 )

0...10V

Z

( -1999  ; 9999 )

0...20mA

Z

( -1999  ; 9999 )

4...20mA

Z

( -1999  ; 9999 )

point position for display

.

It is active if input type of Module-1 is selected

Z

Voltage /Current.

No point
000.0
00.00
0.000

Calibration type

.

It is active if input type of Module-1 is selected

Z

Voltage /Current.

Fixed dual point calibration is performed. Minimum

value of calibration is -1999 and maximum value of

calibration is 9999.
Selectable dual point calibration is performed.

Defines minimum value for selectable dual point calibration.

.

It is active if input type of Module-1 is selected

Z

Voltage /Current.

Defines maximum value for selectable dual point calibration.

.

It is active if input type of Module-1 is selected

Z

Voltage /Current.

Unit selection

Unit is

°C

Unit is

°F

Unit is U

.

No unit.

Minimum value of operating scale (Low Limit). It can be

 

changed according to analog input type and scale.
Maximum value of operating scale (High Limit). It can be

 

changed according to analog input type and scale
Display  offset  for  value  in  analog  input  module.  It  can  be

adjusted from -10% to +10% of scale.

 

This value is added

 

to 

the process value.
It is filter time for input signal. It can be adjusted from 0.0

 

to 

900.0

It determines if the measured value from analog input module

 

in 

Module-1 socket is used as Remote Set or not.

 

This parameter

 

is 

visible if point position and unit parameters are same for

 

process 

input and analogue input module.

Measured value from analogue input module in Module-1

 

socket is used as process set value. User defined process

 

set value is not considered
Measured value from analogue input module in Module-1

socket is not used as process set value. User defined

 

process set value is considered

Summary of Contents for m Series

Page 1: ...ds Programmable ON OFF P PI PD or PID Z OUTPUT 5A 250V 0 4 20 mA V Z Standard Relay Output ADDITIONAL INPUT Extra Analog Input Programmable control or alarm output Electrical Life 100 000 Operation Full Load Extra Relay Output 3A 250V Relay Output Current Input INDICATORS Process Indicators mL PIDC6 10 1 mm Red 4 digit LED Display mL PIDC8 13 2 mm Red 4 digit LED Display Setpoint Indicators mL PID...

Page 2: ... is of the right size Check front panel gasket position 3 Insert the device through the cutout If the mounting clamps are on the unit remove them before inserting the unit to the panel 4 Insert the unit in the panel cut out from the front side 5 Insert the mounting clamps to the holes that are located on top and bottom sides of the device and tighten the fixing screws until the unit is completely ...

Page 3: ...y Access Diagram for Technician Parameters C F V O1 O2 O3 SV REMOTE RAMP MAN AUTO AT C F V O1 O2 O3 SV REMOTE RAMP MAN AUTO AT Main Operation Screen Operator menu entering screen C F V O1 O2 O3 SV REMOTE RAMP MAN AUTO AT SET C F V O1 O2 O3 SV REMOTE RAMP MAN AUTO AT C F V O1 O2 O3 SV REMOTE RAMP MAN AUTO AT SET Press menu button Press menu changing next Button Enter the password with increment and...

Page 4: ...Type Low Point Display adjustment 1999 9999 Unit Active if oltage Current input is selected ZV High Point Display adjustment 1999 9999 Unit Active if oltage Current input is selected ZV Display adjustment points 1999 9999 Unit For example This parameter is active if oltage Current is selected In multi point display adjustment operation defined scale is divided into 16 adjustment points is 0 50 mV ...

Page 5: ...T 0 0 100 0 If heating and cooling PID is used in a system tune operation is performed by heating output Cooling proportional parameter is calculated with heating proportional band value and coefficient P CL P Ht CCoE 100 0 COOLING PROPORTIONAL BAND 000 0 999 9 If Proportional Band Proportional Band 1000 C 0 C and 50 0 ise 100 0 1000 0 50 0 100 0 500 C COOLING INTEGRAL TIME 0000 sec 3600 secs It c...

Page 6: ... 1 socket is EMI 440 Z Voltage Current input type selection This must be selected since analog input module is in Module 1 socket Input Module Selection MODULE 1 Z Z Voltage Current Voltage Current It is active if input type of Module 1 is selected 0 50mV Z 1999 9999 0 5V Z 1999 9999 0 10V Z 1999 9999 0 20mA Z 1999 9999 4 20mA Z 1999 9999 point position for display It is active if input type of Mo...

Page 7: ...e When the value is than 9998 is seen on the display It means alarm latching output is selected It is active if logic output function of Output 3 is alarm output 0 9998 Seconds ýoP1 ConF MODULE 2 Configuration Parameters These devices are equipped with an additional Relay i Output plugged into Module 2 socket Defines output function for Module 2 Heating Cooling Logic output It is active if output ...

Page 8: ...socket Analog Input Modules If you have any of these parameters is observed 2 Sensor Set Point Hýgh Limit sensor scale min 2 Sensor Unit Module 1 or Module 2 socket Analog Input Modules If you have any of these parameters is observed While the motor is completely off the valve fully open While the fully open or fully closed for the pass time required Value between 5 and 600 seconds can be entered ...

Page 9: ...O2 O3 SV REMOTE RAMP MAN AUTO AT SET 9 The device is powered up the normal does not begin to run and the bottom of the screenAs the side flashing Module 1 and Module 2 slots EMIX10 EMI X30 X40 EMI EMI X50 Analog input modules installed at the same time the event occurs The unit normal to return to work the device energy cut off and Analog Input one of the modules must be removed 10 When power is o...

Page 10: ... This symbol is used to determine the dangerous situations as a result of an electric shock User must pay attention to these warnings definitely This symbol is used to determine the important notes about functions and usage of the device Company Information Kessler Ellis Products 10 Industrial Way East Eatontown NJ 07724 Phone 800 631 2165 or 732 935 1320 Fax Email Web 732 935 9344 info kep com ww...

Reviews: