4
ALARM LATCH CANCELING
Alarm latch canceling is not performed.
Display
Function Selection for Top and Bottom Display
It defines the function of the top display.
This parameter determines which value is shown in top
display.
Process value (PV) is shown in top display
Result of subtraction of process set value from process
value (SV-PV) is shown in top display
It defines the function of the bottom display
This parameter determines which value is shown in bottom
display.
Process set value (SV) is shown in bottom display.
%Output value that is applied to process control output is
shown in bottom display.
Configure
Process Input Type and Relevant Parameters with Process Input
Defines the process input
TC input type selection
RTDinput type selection
Z
Voltage/Current input type selection.
Defines type and scale of the thermocouple for TC input. It
is active if TC input type is selected
L (-100°C;850°C)
(-148°F;1562°F)
or
L (-100.0°C;850.0°C)
(-148.0°F;999.9°F)
or
J (-200°C;900°C)
(-328°F;1652°F)
or
J (-199.9°C;900.0°C)
(-199.9°F;999.9°F)
or
K (-200°C;1300°C)
(-328°F;2372°F)
or
K (-199.9°C;999.9°C)
(-199.9°F;999.9°F)
or
R (0°C;1700°C)
(32°F;3092°F)
or
R (0.0°C;999.9°C)
(32.0°F;999.9°F)
or
S (0°C;1700°C)
(32°F;3092°F)
or
S (0.0°C;999.9°C)
(32.0°F;999.9°F)
or
T -200
4
- 8 75
(
°C; 00°C)
( 32 °F; 2°F)
or
T (
°C;
°C)
(
°F;
°F)
-199.9
400.0
-199.9 752.0
or
B (44°C;1800°C)
(111°F;3272°F)
or
B (44.0°C;999.9°C)
(111.0°F ; 999.9°F)
or
E 15
7
23
129 F)
(- 0°C; 00°C)
(- 8°F;
2°
or
E ( 150.0°C;7 .0°C)
( 199.9°F;999.9°F)
-
00
-
or
N ( 200°C;13 °C)
( 328°F;2372°F)
-
00
-
or
N (
°C;999.9°C)
(
°F;999.9°F)
-199.9
-199.9
or
C (0°C;2300°C)
(32°F;3261°F)
or
C (0.0°C;999.9°C)
(32.0°F;999.9°F)
or
Defines type and scale of sensor for RTD input. It is active if
RTD input
PT-100 ( -200°C ; 650°C ) or ( -328°F ; 1202°F)
PT-100 ( -199.9°C ; 650.0°C ) or ( -199.9°F ;999.9°F)
No point
Fixed dual point display adjustment. Display adjustment low
point value is fixed to -1999, display adjustment high point
value is fixed to 9999.
Between second and third digits “0.00”
User can do defined 16 display adjustment points.
Between third and fourth digits “0.000”
Between first and second digits “0.0”
User can do dual point display adjustment with tPoLand tPoH.
Z
Voltage / Current Input Selection
This parameter is active if
Voltage / Current is
Z
selected.
0...50mV
( -1999 ; 9999 )
Z
0...5V
( -1999 ; 9999 )
Z
0...10V
( -1999 ; 9999 )
Z
0...20mA
( -1999 ; 9999 )
Z
4...20mA
( -1999 ; 9999 )
Z
Display Point Position
This parameter is active if
Voltage / Current is selected.
Z
Display ValueAdjustment Type
Low Point Display adjustment (-1999, 9999)Unit
Active if
oltage / Current input is selected.
Z
V
High Point Display adjustment (-1999, 9999)Unit
Active if
oltage / Current input is selected.
Z
V
Display adjustment points (-1999, 9999)Unit
For example :
This parameter is active if
oltage / Current is selected.
In multi point display adjustment operation, defined scale is
divided into 16 adjustment points.
is
(0-50 mV
) .
Z
Z
V
While passing from manual control to automatic control, last process
output value in manual control is accepted as first process output value in
automatic control and automatic control continues to run. Last % process
output value in automatic control is accepted as process output value of
manual control and manual control continues to run.
If there is an alarm output with latching and there is no
alarm status, latching operation will be finished by the
device. When it is finished, this parameter becomes
Automatically
If one of the analogue input modules is plugged in Module-1
or Module-2 socket, measured value from this module input
is shown in top display.
Status of the Ramp/Soak function is shown in bottom
Display.
If one of the analogue input modules is plugged in Module-1
or Module-2 socket, measured value from this module input
is shown in top display.
If CT input module (EMI-420) is plugged in Module-1 or
Module-2 socket, measured value from this module input is
shown in bottom display.
V
rmP SoA:
Configuration of RAMP/SOAK Function and Step SET
Values
Soft-Start
parameter.
When the power is applied to the device,process value
reaches to the set value at the end of this time.
Ramp Soak Tolerance Parameter (%0;%50 Scale)
In Ramp/Soak operation,if process value is out of the
tolerance that is defined with this parameter,then time is
stopped.
Ramp/Soak program step selection parameter.
1.program 1-4 steps
2.program 5-8 steps
Steps between 1-8 is used as one program.
Ramp/Soak step set value.
For ramp operation ; process value reaches to step set values that are
defined with these parameters at the end of the time that are defined in
ramp time parameters. For soak operation ; process value is constant in
step set value that are defined in these parameters for time that are
defined in soak time parameters. Ramp/Soak step set values can be
adjusted from minimum value of set scale to maximum value of set
scale.
Ramp time for Ramp/Soak
Process value reaches to step set values at the end of the
time that are defined in these parameters.
Soak time for Ramp/Soak
Process value is constant in step
set value for time that are defined in these parameters.