8
Alarm Types
Deviation high alarm
HYS
ON
OFF
Process
Set
Process Set
+ Alarm Set
Alarm
Output
Process Value
HYS
ON
OFF
Process Set
- Alarm Set
Alarm
Output
Deviation low alarm
Process Value
HYS
Process Set - Alarm Set
HYS
ON
OFF
Process Set
Process Set + Alarm Set
Alarm
Output
Process Value
Deviation BandAlarm
HYS
Process Set - Alarm Set
HYS
ON
OFF
Process Set
Process Set + Alarm Set
Alarm
Output
Process Value
Deviation RangeAlarm
Process high alarm
HYS
ON
OFF
Alarm
Set
Alarm
Output
Process Value
Alarm Types
Process low alarm
HYS
ON
OFF
Alarm
Set
Alarm
Output
Process Value
Gen ConF: General Parameters
Minimum value for process set and alarm set values
Maximum value for process set and alarm set values
2. Sensor Set Point Low Limit
.sensor scale min. )
2. Sensor Unit
Module-1 or Module-2 socket Analog Input Modules.
(If you have any of these parameters is observed)
2. Sensor Set Point Hýgh Limit
.sensor scale min. )
2. Sensor Unit
Module-1 or Module-2 socket Analog Input Modules.
(If you have any of these parameters is observed)
While the motor is completely off the valve fully open
While the fully open or fully closed for the pass time required.
Value between 5 and 600 seconds can be entered.
(If motorized valve control is selected this parameter is active)
The minimum duration of the valve motor drive output (0.1, 5.0)%
Ultt = 100 sec and
= %1.0 and the motor driving the
valve outlet. The minimum time to be active in 100 * 1.0%=1 sec.
(If motorized valve control is selected this parameter is active)
Com ConF: Parameters for Configuration of Serial Communication
Communication Accessing Address
(1,247)
Communication accessing address of device. It can be
adjusted from 1 to 247.
Communication Baud Rate
1200 Baud Rate.
2400 Baud Rate .
4800 Baud Rate
9600 Baud Rate
19200 Baud Rate
Process Set