991036
08/
13
/19
-
-
-
, mA
- Optional secondary sensor input
- Dual or multi point calibration for
voltage &
Current input
Configurable ON/OFF, P, PI, PD and PID control forms
- Auto-tune and Self-tune PID
- Manual/Automatic mode selection for control outputs
- Bumpless transfer
- Motorized valve control function
- Programmable heating, cooling and alarm functions for control
outputs
-
8 steps profile control ( Ramp & Soak ) function and start-hold
stop by
using logic input module
-
Remote set point function by using analog input modules
- Re-Transmission
mL-PIDC6 & mL-PIDC8
Universal
Input
PID
Process
Controller
s
-
4
digits process
(PV)
and
4
digits process set (SV) display
-
Universal process input(TC, RTD, mV
Z
, V
Z
Z
)
Z
Z
Detection of heater failure by using 0...5
A
V
CT input module
RS-485 serial communication
with Modbus RTU protocol
PROCESS CONTROL
UNITS
mL-PIDC6 & mL-PIDC8
Electrical Connections
SPECIFICATIONS:
Universal Input:
Measurement Range:
:
:
:
CONTROL
(TC) : L(DIN 43710) ,J , K , R , S , T , B , E ve N
(IEC584.1)(ITS90) ,C (ITS90)
(RTD): PT-100 (IEC751)(ITS90)
: mV, V, mA
Please refer to Table-1 for selection of input
type and scal
e
.
Maximum 10 Ohm
Z
Process Inputs
Accuracy:
Cold Junction Compensation
Line Compensation
Sensor Break Protection:
Sampling Cycle
Input Filter :
Control Forms:
Universal input, TC, RTD,
Voltage/Current
Thermocouple
Thermoresistance
Input
± 0,25% of full scale for thermocouple, thermoresistance
and voltage
Automatically ± 0.1°C/1°C.
Upscale
3 samples per second
0.0
to
900.0
seconds
Programmable ON / OFF, P, PI, PD or PID.
Z
OUTPUT
:
5A@250V
-
-0/4...20 mA
V
Z
Standard Relay Output
ADDITIONAL INPUT
Extra Analog
Input
(Programmable control or
alarm output) (Electrical Life : 100.000 Operation (Full Load))
Extra Relay
Output
3A@250V Relay Output
Current Input
INDICATORS
Process
Indicators
:
mL-PIDC6 : 10.1 mm Red
4 digit LED Display
mL-PIDC8 : 13.2 mm Red
4 digit LED Display
Setpoint
Indicators
:
mL-PIDC6 & mL-PIDC8 : 8 mm Green 4 di
g
it LED Display
LED
Indicators
:
AT(Auto
Tuning),
SV(Set
Value),
Man(Manu
a
l
Operation),Auto(Auto
Operation),
O1/2/3
(Output
status
L
ED
s),°C,°F,
V,
Ramp
and
Remote
LEDs
Environmental Ratings and
Physical
Spe
c
ifications
Installation:
Over Voltage Category:
Pollution Degree:
Fixed installation Category II
II
II, office or workplace, none conductive pollution
Operating Temperature:
Max. Operating Humidity
(non-condensing)
Protection Class
NEMA 4X (IP65 at front, IP20 at rear).
0...50°C
0-90%RH
Type-1 Enclosure Mounting
:
:
Mounting:
Weight:
mL-PIDC6 : (48 x 96mm, Depth: 86.5 mm) / (46 x 92mm)
mL-PIDC8 : (96 x 48mm, Depth: 86.5 mm) / (92 x 46mm)
Minimum Distance Between Panel Cut-Out Centers:
mL-PIDC6 : X=65mm, Y=129mm
mL-PIDC8 : X=129mm, Y=65mm
Dimensions / Panel Cut-Out:
Supply Voltage
100-240V
50/60 Hz (-%15;+%10) -6VA
V
V
mL-PICD6 & mL-PIDC8 : 260 gr.
2
1
3
4
5
6
7
9
8
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
TC
0 to 20mA
0 to 50mV
0 to 10V
MODULE - 1
MODULE - 2
Pt-100
5A@250V
OUTPUT - 3
C
NO
NC
CA
T II
Universal
Process Input
(TC, RTD,
V
oltage/Current)
Sensor or T
ransmitter
Supply V
oltage
Output-3
Standard Relay Output
Supply Voltage Input
100-240
VAC
(-15%;+10%)
50/60Hz
- 6V
A
Additional
0/4-20mA
Input
Communication
Socket
24V
±10%
Max.50mA
Additional Relay
Form A
3A@250V
m
LINE