Manual KHS Mini System Control MASTER
11
Ill. 6.7: Exemplary illustration of a CAN bus installation from a -MASTER- and three
-SLAVE- controls
6.2.2.5
Connection of external switch
Attention:
The external connection can only be
used with the KHS Mini System Control
-MASTER-.
Power supply: 230V +/- 15% AC 50/60Hz
Line fuse max. 16A
BK = black = L
Ill. 6.8: Schematic diagram of connection of external switch
Note:
Through the trigger on Terminal 6 you have a facility to switch the
KHS Mini System Control program with external switching processes
through a 230V input. The program switching of the external
connection is discussed in Chapter 8.
230V
L (external voltage)
Switch
CAN bus H and L = 1
Twisted-Pair
H: Strand 1
L: Strand 2
Put on GND cable
shielding
The terminal groups 8/9/10 and
11/12/13 are of equal value. For
instance the wire end a can also be
connected to Terminals 11/12/13 and
the wired end b to Terminals
8/9/10.