Manual KHS Mini System Control MASTER
8
6.2
Electrical installation KHS Mini System Control
The following chapter explains the electrical installation. The electrical connections are
made through screwless-type terminals.
6.2.1
Terminal description -MASTER- and -SLAVE-
Ill. 6.2 Cut-out view of the -MASTER- and -SLAVE- controller board with terminals
Illustration: Control board with terminals
1. Flushing valve switching output 230
________________________
2. Flushing valve voltage output 230 V (only on 68604)
___________
3. Flushing valve N
_______________________________________
4. Power supply - LI 230V
__________________________________
5. Power supply
– N
______________________________________
6. External input 230 V (Function only with -MASTER-)
___________
7. Grounded conductor PE
_________________________________
8. CAN-Bus HIGH 1
______________________________________
9. CAN-Bus LOW 1
_______________________________________
10. CAN-Bus GND 1
______________________________________
11. CAN-Bus HIGH 2
_____________________________________
12. CAN-Bus LOW 2
______________________________________
13. CAN-Bus GND 2
______________________________________
14 Flow measurement valve - Voltage output 5V
________________
15 Flow measurement valve - Flow input
______________________
16 Flow measurement valve - no function _
____________________
17. Flow measurement valve GND
___________________________
18. Pt 1000 Input 1
_______________________________________
19. Pt 1000 Input 2
_______________________________________
20. Pt 1000 Input 3
_______________________________________
21. Pt 1000 Input 4
_______________________________________
22. Drain floating switch (strands interchangeable)
______________
23. Drain floating switch (strands interchangeable)
[Terminals 22 and 23 can also be used to connect
the water sensor]
PC-interface
__________________________
(only for
–MASTER-:
jack plug, no clamp)
24. Alarm relay voltage input external
________________________
25. External monitor voltage error
___________________________
26. External monitor voltage operation
________________________