Electrical Installation
This shower requires a 230-240 VAC, 47 ~ 63Hz single phase supply. A single 3 Amp switched fused spur should be used
for each Panel. Upto 12 Kelda showers can run from a single 32A 30mA RCBO.
Before connecting to power supply, make sure that the mains terminal is able to sustain 240V and 3A.
All electrical installation to
be carried out by an approved electrician in accordance with Part “P” U.K. Building Regulations and to the latest IEEE
standards, or the appropriate regulations in the country of installation.
~~
~~
~~
~~
~~
~~
~~
~~
32A 30mA RCBO
(Up to 12 Showers)
3A Switched Fused Spur
AC 220-240V to DC
36V Transformer 150W
(Supplied)
Control Hub
1.
Thread the power supply cable through the 16mm cable gland in the bottom left of
the Control Hub.
2.
Connect the cable to the 36V power terminal shown. (polarity of connections is not
important)
3.
Using a 3mm flat screwdriver, tighten the connections down and tighten gland nut
onto cable.
Main Distribution Board
230-240V AC
Electrical connection