4.4.5 Assembly of the wires to PUSH IN terminals
NOTICE
Malfunctions caused by loose cable connections!
►
Observe metal sleeve length and stripping length
Cross-section
Wire-end ferrule
Metal sleeve
length
Stripping
length
0.50 mm
2
with plastic collars
)
10 mm
12 mm
0.75 mm
2
12 mm
14 mm
1.00 mm
2
12 mm
15 mm
1.50 mm
2
without plastic collars
)
10 mm
10 mm
0.2…1.5 mm
2
single-wire or fine-wire
without wire-end
ferrule
–
10…15 mm
Table 18: Wire-end ferrules and stripping length
Front view
18
a)
b)
a) Pusher
b) Wire hole
Figure 35: Assembly of the control cable
•
Press pusher by hand. Insert connecting wires into the respective hole, that no
single wires can be seen from the outside or bend outward. A first resistance must
be overcome when inserting. Release the pusher.
•
Check that the connecting wire is fixed and can not be pulled-out. It is important to
ensure that the connecting wire and not the insulation is clamped. The connecting
wire can also be inserted without pressing the pusher in case of cross-sections
upto 1.00 mm².