32
MECHANICAL INSTALLATION
Assembly of the drive converter
For reliable operation, the drive converter must be mounted without any clear-
ance on a smooth, closed, bare metal mounting plate.
3.4.1.1 Mounting instructions for control cabinet installation
The following mounting materials with the appropriate quality must be used to assembly
the drive converters.
Required material
Tightening torque
Socket screw
- M6 x 10 and M6 x 16 - 8.8
5 Nm
45 lb inch
Table 10: Mounting instructions for control cabinet installation
3.4.2
Installation instructions for flat rear heat sink
ATTENTION
Overheating of the device.
Never operate flat rear devices without main cooler.
►
Select suitable cooling surfaces (e.g. water heat sink, ribbed heat
sink, machine base).
► Screw the flat rear of the devices to the cooling surface.
►
Ensure good thermal conductivity (e.g. thermal paste)
►
The machine builder is responsible for the cooling of the units.
Heat-conducting paste
Information about the correct application of the heat-conducting paste are
Select correct flow temperature for liquid coolers
► The flow temperature must be choose in such a way, that no mois
-
ture condensation occurs.
3.4.3 Dimensions central heat sink
3.4.3.1 Air heat sink
Central heat sink for air-cooling upon request.