80
WATer-cOOLeD DeVIceS
Information on coolant management is given in the following
document
www.keb.de/fileadmin/media/Techinfo/dr/an/ti_dr_an-liquid-cooling-00004_
NOTICE
Destruction of the heat sink at storage/transport of water-cooled
devices!
Observe the following points when storing water-cooled devices:
►
Completely empty the cooling circuit
►
Blow out the cooling circuit with compressed air
Destruction of the drive controller due to condensation!
►
Use only NC valves!
5.1.6
Permissible volume flow with water cooling
The volume flow of the following table must be observed.
Permissible
volume flow
Max. volume flow
Q
max
/ l
/min
15
Table 42:
Permissible volume flow with water cooling
NOTICE
Destruction of the heat sink due to erosion !
► The maximum permissible volume flow must not be exceeded.