GB - 25
Connection Power Unit
2.8.4 Temperature detection T1, T2
In.17 Function of T1,
T2
Pn.72
(dr33)
Resistance
Display ru.46
(F6 => ru28)
Error/Warn-
ing
1)
5xh
PTC
(in accord-
ance with
DIN EN 60947-8)
1
< 750 Ω
T1-T2 closed
–
0.75…1.65 kΩ
(reset resistance)
undefined
–
1.65…4 kΩ
(tripping resistance)
undefined
x
> 4 kΩ
T1-T2 open
x
1) The column is valid at factory setting. The function must be programmed accordingly
with parameters Pn.12, Pn.13, Pn.62 and Pn.72 for F5 in operating mode GENERAL.
• Do not lay PTC cable of the motor (also shielded) together with control cable !
• PTC cable inside the motor cable only permissible with double shielding !
2.8.4.1 Use of the temperature input
Wiring example in PTC mode
Thermal contact (NC contact)
T1
T2
Temperature sensor (PTC)
T1
T2
Mixed sensor chain
T1
T2
The function can be switched off with Pn.12 = “7“ (CP.28) if no evaluation of the input is
desired (standard in operating mode GENERAL). Alternatively a bridge can be installed be-
tween T1 and T2.