GB - 13
Technical Data of the 230 V Class
2.2
Technical data of the 230V class
Inverter size
07
09
10
12
Housing size
D
D
D
D
Phases
1
3
1
3
1
3
3
Output rated power
[kVA]
1.6
2.8
4.0
6.6
Max. rated motor power
[kW]
0.75
1.5
2.2
4.0
Output rated current
[A]
4
7.0
10
16.5
Max. short time current
1)
[A]
7.2
12.6
18
29.7
OC-tripping current
[A]
8.6
15.1
21.6
35.6
Input rated current
[A]
8 5.6 14 9.8 20 14 23
Max. permissible main fuse gG
5)
[A]
20 16 20 16 25 20 25
Rated switching frequency
[kHz]
16
16
16
8
Max. switching frequency
[kHz]
16
16
16
16
Power loss at nominal operating
[W]
100
130
170
210
Power loss at DC supply
[W]
90
120
155
185
Standstill current at 4 kHz
2)
[A]
4
7
10
16.5
Standstill current at 8 kHz
2)
[A]
4
7
10
16.5
Standstill current at 16 kHz
2)
[A]
4
7
10
10
Min. frequency at continuous full load
[Hz]
6
6
6
6
Max. heat sink temperature
90 °C (194 °F)
Motor cable cross-section
3)
[mm²] 2.5 1.5 2.5 1.5 4 2.5
4
Min. braking resistor
4)
[Ω]
56
47
33
27
Max. braking current
4)
[A]
7.5
9.5
12
15
Overload characteristic
(see annex A)
Input rated voltage
[V]
230 (UL: 240)
Input voltage range Uin
[V]
180…260 ±0
Input voltage at DC operation
[V]
250…370 ±0
Mains frequency
[Hz]
50 / 60 ±2
permitted mains forms
TN, TT, IT6), ∆-mains7)
Output voltage
8)
[V]
3 x 0…Uin
Output frequency
9)
[Hz]
see control board
Max. motor line length shielded at 4 kHz
[m]
100
100
Max. motor line length shielded at 8 kHz
[m]
50
100
Max. motor line length shielded at 16 kHz
[m]
20
100
1) With regulated systems 5% are to be subtracted as overmodulation capacity
2) Max. current before the OL2 function triggers (not at F5 in operating mode v/f)
3) Recommended minimum cross section of the motor line for rated power and a cable length of upto 100 m
(CU)
4)
This data is only valid for units with internal braking transistor (see "unit identification")
5) Protection in accordance with UL see annex B
6) IT system optional
7)
Phase conductor grounded mains are only permissible without HF filters
8) The voltage at the motor is dependent on the series-connected units and on the control method (see A.3)
9) The output frequency is to be limited in such way that 1/10 of the switching frequency is not exceeded
The technical data are for 2/4-pole standard motors. With other pole numbers the inverter
must be dimensioned onto the motor rated current. Contact KEB for special or medium fre-
quency motors.