GB - 12
Technical Data
2.
Technical Data
2.1
Operating conditions
Standard
Standard/
class
Instructions
Definition acc.
EN 61800-2
Inverter product standard:
rated specifications
EN 61800-5-1
Inverter product standard:
general safety
Site altitude
max. 2000 m above sea level
(over 1000 m a derating of 1 % per 100 m must be taken
into consideration).
Ambient conditions during operation
Climate Temperature
EN 60721-3-3
3K3
extended to -10…45 °C (use frost protection for water
cooling systems and temperatures below zero)
3)
Humidity
3K3
5…85 % (without condensation)
Mechanical
Vibration
3M1
Contamination
Gas
3C2
Solids
3S2
Ambient conditions during transport
Climate Temperature
EN 60721-3-2
2K3
Drain heat sink completely
Humidity
2K3
(without condensation)
Mechanical
Vibration
2M1
Surge
2M1
max. 100 m/s²; 11 ms
Contamination
Gas
2C2
Solids
2S2
Ambient conditions for the storage
Climate Temperature
EN 60721-3-1
1K4
Drain heat sink completely
Humidity
1K3
(without condensation)
Mechanical
Vibration
1M1
Surge
1M1
max. 100 m/s²; 11 ms
Contamination
Gas
1C2
Solids
1S2
Type of protection
EN 60529
IP20
Environment
IEC 664-1
Pollution degree 2
Definition acc.
EN 61800-3
Inverter product standard:
EMC
EMC emitted interference
Cable-based interferences
–
C2
1) 2)
Earlier limit value A (B optional) according to EN55011
Radiated interferences
–
C2
2)
Earlier limit value according to EN55011
Interference immunity
Static discharges EN 61000-4-2
8 kV
AD (air discharge) and CD (contact discharge)
Burst - Ports for process meas-
urement control lines and signal
interfaces
EN 61000-4-4
2 kV
Burst - power interfaces EN 61000-4-4
4 kV
Surge - power interfaces EN 61000-4-5
1 / 2 kV
Phase-phase / phase-ground
Electromagnetic fields
EN 61000-4-3
10 V/m
Cable-fed disturbances, induced
by high frequency fields
EN 61000-4-6
10 V
0.15-80 MHz
MM
Voltage variation /
voltage drop EN 61000-2-1
3
+10 % -15 %
90 %
Voltage unsymmetries /
Frequency changes EN 61000-2-4
3
3 %
2 %
1)
This product can cause high frequency disturbances in residential areas (category C1) which require noise suppression measures.
2)
The specified value is only meet in connection with a corresponding filter.
3)
Depending on the operating conditions and corresponding power reduction, higher temperatures are permissible after consulting KEB.
Summary of Contents for COMBIVERT F5
Page 2: ......