KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118 

This manual is for qualified personnel only     

 

Page  41 

6.5

 

Appendix 5 BAT_T communication port   

Definition of port

 

 

 

Connection between the Temperature senator RJ45 port and UPS RJ45 port. 

 

Device (RJ45) 

UPS (RJ45) 

Description 

Pin 1/5 

Pin 1/5 

485+ “A”   

Pin 2/4   

Pin 2/4 

485 - “B” 

Pin7 

Pin7 

+12Vdc 

Pin8 

Pin8 

GND 

 

Available function of BAT_T 

 

  Battery environment temperature monitoring. 

  Charging voltage modulation depending on batteries’ temperature.

 

 

6.6

 

Appendix 6 Optional port   

Definition of Male port

 

 

 

 

Instruction: 

UPS 

Instruction 

Pin1 

UPS Battery Low 

Pin2 

AC Power Failure 

Pin3 

Turn off UPS 

Pin4 

Common GND 

 

Function 1 description (Optional): 

 

  Drive the bypass breaker when feedback alarm. 

 

Function 2 description (Optional): 

 

  Drive the battery breaker when battery voltage low. 

 

 

Summary of Contents for T SERIES

Page 1: ...OR OTHER DOCUMENTATION B ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES DAMAGES COSTS OR EXPENSES WHETHER SPECIAL DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT OF THE USE OF SU...

Page 2: ...ces 10 3 6 Power Cables 10 3 7 Power cable connections 11 3 8 Internal Battery Connection 14 3 9 External Battery Connection 15 3 10 UPS Parallel Installation 17 3 11 Computer access 18 4 Operation 19...

Page 3: ...when the input AC power is disconnected WARNING No User serviceable Parts Risk of electrical shock do not remove cover No user serviceable parts inside Refer servicing to qualified service personnel...

Page 4: ...source from ground WARNING Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if groundings are removed during installation and mai...

Page 5: ...enhances and increases reliability performance self protection self diagnostics and so on Charging Current is configurable Using the PC Software the user may set the capacity of the batteries as well...

Page 6: ...acceptance file a claim for concealed damage with the carrier Unpacking the UPS in a low temperature environment may cause condensation to occur inside the UPS enclosure To reduce the hazard of electr...

Page 7: ...6 5492 Keatec T Series 10 20kVA PF1 0 208Vac with Internal Battery 7 0 Touch Screen Users Guide English 20181118 This manual is for qualified personnel only Page 6 3 2 Cabinet Overview Front View Side...

Page 8: ...ver 1 LCD panel LEDs 2 Intelligent Slot 1 SNMP card Relay card 3 Intelligent Slot 2 SNMP card Relay card 4 Dry contact port 5 Power Switch 6 USB port 7 RS485 port 8 RS232 port 9 O P Switch 10 Maintena...

Page 9: ...cover 1 LCD panel LEDs 2 Intelligent Slot 1 SNMP card Relay card 3 Intelligent Slot 2 SNMP card Relay card 4 Dry contact port 5 Power Switch 6 USB port 7 RS485 port 8 RS232 port 9 O P Switch 10 Mainte...

Page 10: ...hould be installed Air filters should be used to prevent from dust entering the UPS The environment temperature around the UPS should in the range of 0 40 C If the environment temperature exceeds 40 C...

Page 11: ...over current through a DC compatible thermo magnetic circuit breaker or a set of fuses located close to the battery UPS Output Any external distribution board used for load distribution shall be fitt...

Page 12: ...able Connect each cabinet to the main ground system For Grounding connection follow the shortest route possible WARNING Failure to follow adequate earthing procedures may result in electromagnetic int...

Page 13: ...ine IN OUT Input Output Output L1 Output Phase L1 Input L1 Primary input Phase L1 Output L2 Output Phase L2 Input L2 Primary input Phase L2 Output L3 Output Phase L3 Input L3 Primary input Phase L3 Ou...

Page 14: ...put N Input Neutral for primary and secondary input GND Grounding Bps L1 Secondary input Phase L1 BAT Positive terminal of the battery string Bps L2 Secondary input Phase L2 BATN Neutral terminal of t...

Page 15: ...the equipment below the power connections All cabinets in the UPS must be grounded properly CAUTION The earthing and neutral bonding arrangement must be in accordance with local and national codes of...

Page 16: ...tteries installation 3 9 External Battery Connection The UPS adopts positive and negative double battery framework with 20pcs in series A neutral cable is retrieved from the joint between the cathode...

Page 17: ...settings can be done through LCD panel or monitoring software CAUTION Ensure correct polarity battery string series connections I e inter tier and inter block connections are from to terminals Do not...

Page 18: ...n the parallel system as below Make sure each UPS input breaker is in the off position and there is no output from any of the UPS Battery groups can be connected separately or in parallel which means...

Page 19: ...ll the UPS modules must be connected to a common output bus 4 The length and specification of power cables including the bypass input cables and the UPS output cables must be the same This facilitates...

Page 20: ...nverter before using the PC Software to set the output voltage and frequency 4 Operation 4 1 Operation Modes The UPS is a double conversion on line UPS that may operate in the following modes Normal m...

Page 21: ...of unsynchronized AC sources This interruption is programmable but typically set to be less than an electrical cycle e g less than 15ms 50Hz or less than 13 33ms 60Hz ECO Mode When the UPS is at AC M...

Page 22: ...up after 4 Switch ON UPS output switch If the rectifier fails at start up the bypass LED will light up When the inverter starts up the UPS will transfer from bypass mode to inverter mode and then the...

Page 23: ...ill supply to the load through the MAINTENANCE breaker Switching to normal operation from mechanical bypass CAUTION Do not attempt to switch the UPS back to normal operation until it has been verified...

Page 24: ...there should be no output On line mode 1 Press OFF to shut down the UPS wait about 30s 2 Open the BATTERY breaker 3 Open the battery power switch for standard UPS 4 Switch to OFF the AC input breaker...

Page 25: ...24 4 2 6 Parallel Settings 1 Connect the UPS to the computer 2 Power on the UPS 3 Open Muser4000 software click System then select User Set 4 From User Set window click Set 5 From the Data Set window...

Page 26: ...ow select Ups ID and put the ID value for the parallel UPS in the box on the right side Click Set to save the values as shown below The UPS will sound a beep to indicate that the setting has been corr...

Page 27: ...setting 4 Turn off the input breaker of Unit 1 and make sure the UPS is off Turn on the input breaker of Unit 2 access the LCD setting interface setting the parallel working mode ID NO 2 parallel 4 u...

Page 28: ...he UPS by flow chart Touch the bypass icon to enter the bypass data window touch the back icon return to last window and touch the homepage icon jump to main page Touch the mains icon to enter the mai...

Page 29: ...nternal Battery 7 0 Touch Screen Users Guide English 20181118 This manual is for qualified personnel only Page 28 Touch the battery icon to enter the battery data window touch the back icon return to...

Page 30: ...personnel only Page 29 4 3 2 Run Info From the Home page touch the Run info icon to enter the information page Touch the Status Information icon to enter the status data window click the back icon ret...

Page 31: ...ata window touch on the back icon return to last window and touch on the homepage icon jump to main page Touch the history icon to enter the history window can see the history data touch the back icon...

Page 32: ...for qualified personnel only Page 31 4 3 5 Maintenance Touch Maintenance icon to enter setting page touch the back icon return to last window and touch the homepage icon jump to main page 4 3 6 Functi...

Page 33: ...GUISH 12 Fault Mode LIGHT X X X CAUTION X means it is determined by other conditions Alarm Information Fault code Err UPS Alarm Warning Buzzer LED 1 Rectifier Fault Beep continuously Fault LED lit 2 I...

Page 34: ...second Fault LED blinking 30 Rectifier over current Once per second Fault LED blinking 31 Bypass over current Once per second BPS LED blinking 32 Overload Once per second INV or BPS LED blinking 33 N...

Page 35: ...PP function to enable the remote control via the internet when the network is unavailable In addition to the features of a standard NetAgent Mini NetAgent II has the option to add NetFeeler Lite to de...

Page 36: ...25 of nominal output current IEC 60947 2 curve C Current rating of neutral cable A 1 7 In Generator Input Support OUTPUT Inverter Output Power factor 1 0 Rated AC Voltage 1 208 120Vac or 220 127Vac 50...

Page 37: ...sfer Asynchronous transfer 15ms 50 Hz 13 3ms 60 Hz Alarms overload utility abnormal UPS fault battery low etc Protection short circuit overload over temperature battery low fan fault alarm Communicati...

Page 38: ...ure the output cable is well connected Switch ON output breaker 4 Utility LED is flashing Utility voltage exceeds UPS input range If the UPS operates in battery mode pay attention to the remaining bac...

Page 39: ...SB port PC USB port UPS USB port Description Pin 1 Pin 1 PC 5V Pin 2 Pin 2 PC DPLUS signal Pin 3 Pin 3 PC DMINUS signal Pin 4 Pin 4 Signal ground Available function of USB Monitor UPS power status Mon...

Page 40: ...rt and UPS RS232 port PC RS232 port UPS RS232 port Pin 2 Pin 2 UPS send PC receive Pin 3 Pin 3 PC send UPS receive Pin 5 Pin 5 ground Available function of RS232 Monitor UPS power status Monitor UPS a...

Page 41: ...Pin 1 5 485 A Pin 2 4 Pin 2 4 485 B Pin7 Pin7 12Vdc Pin8 Pin8 GND Available function of RS485 Monitor UPS power status Monitor UPS alarm info Monitor UPS running parameters Timing off on setting Batte...

Page 42: ...ion Pin 1 5 Pin 1 5 485 A Pin 2 4 Pin 2 4 485 B Pin7 Pin7 12Vdc Pin8 Pin8 GND Available function of BAT_T Battery environment temperature monitoring Charging voltage modulation depending on batteries...

Page 43: ...ction diagram Connection between the button and UPS REPO port Button UPS REPO Description Pin 1 Pin 1 EPO Pin 2 Pin 2 GND A remote emergency stop switch Dry contact signal and normally open not provid...

Reviews: