background image

 

V1.01 

 

 

 

 
 

USER MANUAL V1.01 

 

 

PB.UPS.2.2.24(.Li) 

PB.UPS.3.5.24(.Li) 

PB.UPS.5.5.48(.Li) 

PB.UPS.10.10.48(.Li) 

PB.UPS.15.15.48(.Li) 

 

 

 

Summary of Contents for LfeLi-48100TB

Page 1: ...V1 01 1 USER MANUAL V1 01 PB UPS 2 2 24 Li PB UPS 3 5 24 Li PB UPS 5 5 48 Li PB UPS 10 10 48 Li PB UPS 15 15 48 Li...

Page 2: ...THE PROGRAMMING THAT CAN ACTIVATE THIS THE PB UPS SYSTEMS ARE PROVIDED AS A WHOLE CONSISTING OF INVERTER BATTERIES BATTERY BOX CABLES AND ACCESSORIES FUSES IT IS IMPORTANT THAT THE SYSTEM IS INSTALLE...

Page 3: ...g the device 16 Battery connection 17 Recommended battery cable and terminal size 18 AC input output terminal 18 PV connection 20 PV module selection 21 final assembly 23 Communication Connection 23 E...

Page 4: ...charge voltage 34 Program 19 battery minimum voltage settings 35 Program 20 switch from battery to utility discharge 35 Program 21 switch from battery to utility charge 35 Program 22 Automatic Page Tu...

Page 5: ...el in mono phase setup 54 Three phase setup 56 Connecting solar panel 57 Error reference code 57 Settings 58 Parallel in mono phase PB UPS 10 10 48 PB UPS 15 15 48 58 Three phase configuration PB UPS...

Page 6: ...g characteristic 74 charging voltage 75 Temperature compensation 75 STORAGE 76 Environment 76 Self discharge 76 OCV versus SOC 76 Recharging 77 LIFESPAN 78 Lifespan at Floating 78 Lifespan at Deep Cyc...

Page 7: ...antling 88 USING FeLiPo4 BATTERIES 88 Charging 88 Discharging 89 USE OF THE BLUETOOTH APP 89 GRAPHS 92 FAQ 95 POSSIBLE ERRORS AND THEIR CORRECTION 96 WARRANTY HANDLING 97 SERVICE 98 SPECIFICATIONS PB...

Page 8: ...115 INSTALLATION GUIDE 116 Installation Precautions 116 Preparation of the installation 119 Installation and cabling 121 Standard installation of the cabinet 121 Electrical maintenance 122 Battery mai...

Page 9: ...5 5 48 147 PB UPS 10 10 48 151 PB UPS 15 15 48 156 PB UPS 2 2 24 Li 161 PB UPS 3 5 24 Li 165 PB UPS 5 5 48 Li 169 PB UPS 10 10 48 Li 173 PB UPS 15 15 48 Li 177 MOUNTING FUSEHOLDERS AND BUSBAR 181 BUSB...

Page 10: ...V1 01 10...

Page 11: ...V1 01 11 PB UPS 2K24 PB UPS 3K24 PB UPS 5K48...

Page 12: ...V1 01 12...

Page 13: ...al power supply conditions or operate environmental damage SAFETY INSTRUCTIONS WARNING This chapter contains important safety and operating instructions Read and keep this manual for future reference...

Page 14: ...ls Please refer toINSTALLATION section of this manual for the details 10 Fuses 1 piece of 200A 58VDC for 3KW 4KW and 5KW are provided as over current protection for the batterysupply 11 GROUNDING INST...

Page 15: ...not in use 5 Function buttons 13 Parallel communication port 6 Power on off switch 14 Parallel dipswitches 7 AC input utility 15 Potential free contact 8 AC output loads 16 USB INSTALLATION Unpacking...

Page 16: ...is inverter at eye level in order to allow the LCD display to be read at all times For proper air circulation to dissipate heat allow a clearance of approx 200 mm to the side and approx 300 mm above a...

Page 17: ...st be done by qualified personnel warning It is very important for system safety and efficient operation to use suitable cable for battery connection To reduce the risk of injury use the the correct r...

Page 18: ...ls until the terminals are properly connected PAY ATTENTION Before making final DC connection or closing DC breaker disconnector must be connected to positive and negative must be connected to negativ...

Page 19: ...ow to implement ac input output connection 1 Before making ac input output connection please open the DC protector or decoupler first 2 Remove insulation sleeve 10mm for six conductors And shorten pha...

Page 20: ...ind of damage check with the manufacturer of the air conditioner if it is equipped with an installation delay function Otherwise this inverter charger will cause overload error and turn off the output...

Page 21: ...everal PV modules in series connection See the table below Note Vmp panel max power point voltage PV charging efficiency is maximized when the PV system voltage is close to the Best Vmp Maximum PV mod...

Page 22: ...tive and negative conductors 2 Check the correct polarity of the connection cable of PV modules and PV input connectors Then connect the positive pole of the connection cable to the positive pole of t...

Page 23: ...t inverter and PC Insert a supplied CD into a computer and follow the on screen instructions to install the installing surveillance software Consult the software user manual in the CD for the detailed...

Page 24: ...switch located on the button on the case to turn on the device Control and display panel The control and display panel shown in the graph below is located on the front panel of the drive It includes t...

Page 25: ...ter Flashing Warning condition occurs in the inverter Function Keys Function Keys Description menu Enter reset mode or setting mode go to previous selection up Increase the setting data down Decrease...

Page 26: ...battery charging status STATUS Constant Currentmode Constant Voltage mode Battery voltage LCD display 2V cel 4 bars will flash in turns 2V cel 2 083V cel Bottom bar will be on and the other threebars...

Page 27: ...l 1 817V cel 1 9V cell 1 9V cel 1 983V cell 1 983V cell load 20 1 867V cell 1 867V cell 1 95V cell 1 95V cell 2 033V cell 2 033V cell Load Information Indicates overload Indicates the load level by 0...

Page 28: ...ration Indicates unit alarm is disabled LCD Setting After pressing and holding ENTER button for 2 seconds the unit will enter setting mode Press UP or DOWN button to select setting programs And then p...

Page 29: ...age or the setting point in program 20 or solar and battery is not sufficient The battery energy will supply power to the load in the condition of theutility is unavailable or the battery voltage is h...

Page 30: ...range will be between 90 and 280VAC UPS When selected the acceptable ac input voltage range will be between 170 and 280VAC GEN When the user uses the device to connect the generator select the generat...

Page 31: ...ply the load or charge the battery it will NOT supply to the grid LBU Solar energy supplies power to the loads as the first priority If the battery voltage is lower than the set point in program 20 th...

Page 32: ...RE Opnieuw opstarten inschakelen Program 09 inject to the grid not applicable Program 10 priority charging CSO Solar energy first Solar energy charges the battery as the first priority The utility pow...

Page 33: ...m 13 set utility charging current Settings per system PB UPS 2 2 24 50A PB UPS 2 2 24 Li 50A PB UPS 3 5 24 50A PB UPS 3 5 24 Li 50A PB UPS 5 5 48 50A PB UPS 5 5 48 Li 50A PB UPS 10 10 48 100A PB UPS 1...

Page 34: ...rogram 17 set bulk charging voltage PB UPS 2K24 PB UPS 3K24 PB UPS 5K48 If user defined is selected in program 14 this program can be set The setting range is from 24 0V to 29 2V for 24Vdc model and 4...

Page 35: ...set point regardless of the percentage of the load that is connected Program 20 switch from battery to utility discharge PB UPS 2K24 PB UPS 3K24 PB UPS 5K48 Battery stops discharging voltage when gri...

Page 36: ...page PTD If selected the display screen will stayat latest screen user finally switches Program 23 Backlight control LON backlight on LOF backlight off Program 24 alarm control BON alarm on BOF alarm...

Page 37: ...working status SBD balancing solar power disable if selected the solar power input will be equal to the maximum charging capacity of the battery regardless of the number of consumers connected The ma...

Page 38: ...available for 48V systems 57 6V These options do not apply to the PB UPS systems Program 32 not applicable Program 33 time battery equalization The setting range is from 5 minutes to 900 minutes The...

Page 39: ...battery equalization will be activated immediately and EQ appears on the LCD main page If ADS is selected the equalization function will be canceled until the next activated equalization time starts...

Page 40: ...V1 01 40 Programming via PC TOOL Main window when connected to live PB UPS via USB cable The main window shows the general operating status dashboard To access the settings login with default password...

Page 41: ...configuration buttons appear all parameters were organized as Charger and Inverter inverter And there is a button to reset all current configurations to defaults Here are the parameters in 2 configur...

Page 42: ...verter output voltage is high 07 Overload time out 08 Inverter bus voltage is too high 09 Bus soft start failed 11 Main relay failed 21 Inverter output voltage sensor error 22 Inverter grid voltage se...

Page 43: ...under frequency 44 Inverter grid over frequency 51 Inverter over current protection error 52 Inverter bus voltage is too low 53 Inverter soft start failed 55 Over DC voltage in AC output 56 Battery co...

Page 44: ...Solar charger over temperature 76 PV charger communication error 77 Parameter error Beschrijving bedrijfsstatus Solar energy is higher than required power Solar energy is lower than required power Sol...

Page 45: ...ery Off grid status energy comes from the battery The inverter stops working if you disconnect the inverter turns off with the soft key or if an error has occurred in the state in which it does not wo...

Page 46: ...soidal utility or generator Nominal Input Voltage 230Vac Low Loss Voltage 90Vac 7V APL GEN 170Vac 7V UPS 186Vac 7V VDE Low Loss Return Voltage 100Vac 7V APL GEN 180Vac 7V UPS 196Vac 7V VDE High Loss V...

Page 47: ...tage regulation batt mode 220Vac 240Vac adjustable efficiency peak 93 Transfer time 10ms UPS VDE 20ms APL AC input Voltage Vac 230 Adjustable voltage range 170 280 Vac for personal computers 90 280Vac...

Page 48: ...00 298 468 125 PB UPS 2K24 PB UPS 3K24 PB UPS 5K48 Low DC Warning Voltage At load 20 22 0Vdc 44 0Vdc 20 load 50 21 4Vdc 42 8Vdc At load 50 20 2Vdc 40 4Vdc Low DC Return Voltage Warning At load 20 23 0...

Page 49: ...he battery is reversed Entry guard is activated 1 Check that the batteries and cables are connected properly 2 Recharge the battery 3 Replace the battery Mains power present but the device is running...

Page 50: ...2 Internal temperature of inverter component is over 90oC Check whether the air flow of the unit is blocked or whether the ambient temperature is toohigh Fault code 03 Battery is over charged Return t...

Page 51: ...tput voltage is unbalanced happens again please returnto repair center Fault code 56 Battery is not connected well or fuse is burnt If the battery is connected well please return to repair center Gesc...

Page 52: ...2 Up to three units work together to support three phase equipment The maximum output power supported is 15kVA package contents Inside the box you will find the following items in the package Buildin...

Page 53: ...tes the number of inverters connected in parallel Regarding net and load please also follow the same principle PAY ATTENTION Install the circuit breaker on the battery and mains side This will ensure...

Page 54: ...inverters share the same battery bank Otherwise the inverters will switch to fault mode Parallel in mono phase setup PB UPS 10 10 48 Connection communication Inverter 1 set button 1 of the DIP switch...

Page 55: ...d buttons 2 3 4 5 of the DIP switch in the upper position Inverter 2 set the button 2 of the DIP switch to the lowest position and the button 1 3 4 5 of the DIP switch in the top position Inverter 3 s...

Page 56: ...button 1 3 of the DIP switch to the lower position and the buttons 2 4 5 of the the DIP switch in the upper position Inverter 2 set the button 2 3 of the DIP switch to the lower position and the butto...

Page 57: ...eparately Fault reference code 80 CAN fault 81 Host loss 82 Synchronization loss 83 Battery voltage detected different 84 AC input voltage and frequency detected different 85 AC output current unbalan...

Page 58: ...re connected to each other STEP 2 On the bottom panel of the inverter there are 5 pin DIP switches you can set it as follows in the figure below REMARK 1 If there are two inverters in parallel you onl...

Page 59: ...en on SLAVE inverter STEP 5 When there is no more fault alarm the parallel system is fully installed STEP 6 Turn on all circuit breakers from the cabling to the load side This system will start supply...

Page 60: ...lly Otherwise the AC icon will flash and they will not work in line mode LCD display in L1 LCD display in L2 LCD display in L3 STEP 5 When there is no more fault alarm the system is to support 3 phase...

Page 61: ...ck the utility wiring connection and restart the inverter 85 AC output current unbalance Restart the inverter 86 AC output mode setting is different Turn off the inverter and check the DIP setting 87...

Page 62: ...V1 01 62...

Page 63: ...V1 01 63 PB SC12 170...

Page 64: ...V1 01 64...

Page 65: ...nt are defined as follows Danger that can cause serious injuries or even death Used to indicate potential danger it may cause death or serious injury if not avoided Used to indicate medium or low pote...

Page 66: ...ulations before you start Pre Installation Requirements Only qualified persons with adequate training and familiar with all safety regulations may install operate or maintain PB SC 12 170 batteries In...

Page 67: ...ce Modular design and installation for less space easy installation maintenance UL94 V0 ABS Container Integrating Gel and AGM technology there is no liquid electrolyte Oxygen recombination efficiency...

Page 68: ...n 12 12Vdc 170 170Ah C10 2 0kWh energy at 100 discharge DOD100 at C10 1 3kWh energy at 60 discharge DOD60 at C10 C10 according to EUROBATNORM discharge at 10 of the Capacity 17A for 10 hours from 100...

Page 69: ...m bulging Container Contains the electrolyte plates etc Keep the poisonous out and active material in so that the reaction could carry on Also it helps ventilation It is made from strong plastic mater...

Page 70: ...25 Low selfdischarge The self discharge rate of LRC batteries is less than 3 of rated capacity at 20 25 storage temperature This low self discharge rate indicates a storage time under the aforementio...

Page 71: ...The oxygen which is generated from the positive electrode will travel through the separators to the negative electrode to oxidize the Pb sohygrogen generation is controlled This recombination process...

Page 72: ...discharge current the more the discharge capacity will be increased The larger the discharge current the lower the discharge capacity will be decreased C10 means the rated capacity discharged at 25 w...

Page 73: ...arge curve the voltage will drop rapidly when it reaches critical and little energy can be harvest if we continue to discharge it will has some bad influence on the battery So the discharge must be st...

Page 74: ...IFICATIONS Charge characteristic The figure below shows the constant charging characteristic the charging voltage increases with the charging time However at the final stage the charge voltage will in...

Page 75: ...Storage time above 3 months or longer In battery group when the float charge voltage of one unit is below 2 16V Cell New battery is installed and debugged but not in operation model yet Float charge...

Page 76: ...risk for fire and explosion so keep them away from fire heater or organic solvent Keep the batteries under dry cool environment when they are stored Please recharge the batteries using the instructio...

Page 77: ...e produced in the battery negative plate this is called sulfate after they were stored for a long time Because lead sulfate is an insulator it will influence the performance of the charge therefore it...

Page 78: ...increasewith the increasement of the temperature andcharge current The estimate battery float life can be judged by the standard high temperature accelerated life test The actual float life is affect...

Page 79: ...he actual cycle life is depends on DOD and some other conditions ENVIRONMENT PROTECTION Toxic and poison Recycle This mark indicates that the product can not be classified with other waste In order to...

Page 80: ...ontainer material ABS Nominal capacity 25 C 174Ah 10 uur 17 4A 1 80V cell 146 5Ah 5 uur 29 3A 1 75V cell 131 1Ah 3 uur 43 7A 1 75V cell Short circuit current 1706A Internal resistance 25 C 4 0m Temper...

Page 81: ...V1 01 81 PB Li 12 100D...

Page 82: ...V1 01 82...

Page 83: ...attery Avoid short circuits as the terminals are always live avoid direct connection of the terminals to each other Do not place tools or objects on the battery Only extinguish with class D fire extin...

Page 84: ...sposal LiFePO4 batteries should not be disposed of with household or commercial waste registered but must be handed in for disposal recycling at the collection points of the common take back system Th...

Page 85: ...ages over lead acid batteries including lead acid AGM and GEL batteries and lithium batteries from other manufacturers Only about 40 50 of the weight of a lead acid battery of the same capacity Integr...

Page 86: ...ther mobile applications Consumable battery or propulsion battery in boats emergency power supply BMS Battery Management System The Battery Management System integrated into every PowerBoozt LiFePO4 b...

Page 87: ...urces Charge before use the battery is only charged to 40 60 during transport Series parallel connection PowerBoozt LiFePO4 batteries can be connected in series and or parallel note Before installatio...

Page 88: ...he battery isolating switch to avoid to prevent discharge via hidden consumers If the battery is stored removed the terminals must be covered with a protective cap or be masked Ideal is storage in a d...

Page 89: ...perature drops it automatically switches the battery back on The balancing of the cells is done automatically during loading or if necessary during a standby phase Discharging Discharge to 100 of capa...

Page 90: ...name of the battery if assigned and the MAC address of the Bluetooth module By tapping your battery s MAC address You can find the MAC address of your battery on the small sticker on the battery make...

Page 91: ...sed so far Congestion Indicators Green OK Red Error Overvoltage Under pressure Charging current too high Discharge current too high Temperature too low while charging Temperature too low when discharg...

Page 92: ...V1 01 92 GRAPHS discharge graph Discharge with different currents at 25 C Discharge at different temperatures...

Page 93: ...V1 01 93 Charging graph State of charge SOC with 0 5C at 25 C Charging characteristic with 0 5C at 25 C...

Page 94: ...V1 01 94 Longevity and Self discharging graph Number of Cycles with 1C Self discharge at different temperatures...

Page 95: ...the contrary Fully charge the battery to approx 60 80 and then disconnect or disconnect the battery from the vehicle In my vehicle it sometimes gets to 50 C and more in the summer Will it damage my l...

Page 96: ...switch off the inverter However the maximum continuous discharge current of the battery must not be exceeded Can I extend lithium batteries with parallel connection of other batteries Yes provided th...

Page 97: ...RANTY HANDLING All POWERBOOZT batteries are manufactured according to the strictest quality criteria and POWERBOOZT guarantees that the LiFePO4 batteries are delivered in perfect condition POWERBOOZT...

Page 98: ...uick handling If possible use the original packaging as a shipping box If you no longer have the original packaging make sure you have enough protection against transport damage with suitable UN certi...

Page 99: ...continuous discharge current 100A Peak discharge current 200A 4 5 seconds 2 5seconds BMS shutdown on discharge 250A 50A Recommended Shutdown 11V Back on 11 2V Charge Recommended charging current 50A M...

Page 100: ...V1 01 100...

Page 101: ...V1 01 101 LfeLi 48100TB...

Page 102: ...V1 01 102...

Page 103: ...in this document are defined as follows Danger that can cause serious injury or even death Used to indicate potential danger could be death or serious cause injury if not avoided Used to indicate medi...

Page 104: ...ormance Battery with respect for safety and environment that can be used in harsh outdoor environments The system also includes an advanced Battery Management System BMS which is responsible is for ma...

Page 105: ...V1 01 105 Product structure LFeLi frontpanel...

Page 106: ...of the battery via light indicator Capacity 75 100 50 75 25 50 0 25 indication for on indication for out ALM RUN RUN en ALM indicates battery status Function interpretation color blink frequency Indi...

Page 107: ...Pack2 OFF OFF ON OFF 4 PACK3 Use as SlavePack3 ON OFF ON OFF 5 PACK4 Use as SlavePack4 OFF ON ON OFF 6 PACK5 Use as SlavePack5 ON ON ON OFF 7 PACK6 Use as SlavePack6 OFF OFF OFF ON 8 PACK7 Use as Slav...

Page 108: ...module can see a unit with any address but a single unit can be seen with RS232 not all units in the package Software and manual are supplied with the unit on a CD RS485 When the system is in parallel...

Page 109: ...rge and discharge over low temperature OUTPUT exit A total of 4 output terminals 2 positive and 2 negative marked P P Each clamp has the specification for M8 Stud Required Torque Settings 6 1N 7 5N MC...

Page 110: ...nu keys The functions are described below Display function keys Main menu Confirm enter Page up Page down Return launch Operating procedures 1 Press once the LCD screen lights up and the welcome inter...

Page 111: ...Then click again to go to the main menu bar 3 Scroll page up and page down go to it Menu screen when the arrow points to the corresponding bar press Enter to to confirm 4 Go back to the menu bar and...

Page 112: ...to add new features or fix a bug POWERBOOZT provides the software to upgrade the battery firmware When upgrade first make sure the BMS product is in standby state Please switch off charger and consume...

Page 113: ...the button Upgrade to perform the upgrade After opening the upgrade tool the first upgrade will ask The upgrade is complete Are you sure you want to upgrade Click OK to continue the upgrade and there...

Page 114: ...ng overcurrent the discharge change from charge to discharge and vice versa The monitoring module monitors the equilibrium function and the power the temperature and the SOC The control module transmi...

Page 115: ...ransportation the battery may enter sleep mode to avoid the loss of capacity to decrease Easily accessible front connectors to facilitate installation of one or more units Lightweight convenient size...

Page 116: ...e management parameters and the output parameters of the switching power system INSTALLATION GUIDE Installation Precautions Comply with local laws and regulations Be sure to follow local laws and regu...

Page 117: ...e safety of the system and personnel 2 fire protection No flammable explosive or other dangerous goods may be stored in the room and the room must be equipped with effective fire equipment such as CO2...

Page 118: ...ll the module in dusty dirty environments Do not place any objects on top of the lithium ion battery People should never be on the battery sit or stand Check power Before installation check the load c...

Page 119: ...sories are shipped in cardboard or wooden boxes When unpacking be careful when disassembling Check that the device and accessories correspond to the packing list and that nothing during the shipment w...

Page 120: ...Measuring tape Drilling machine Gereedschap voor levering en uitpakken Manual Forklifts Electric Forklift support ring weight 400kg Leverage weight 400kg Electrical installation tools Insulated gloves...

Page 121: ...attery and turn off the rectifier without plugging in the mains to switch The battery must be recharged for normal operation Standard installation of the cabinet Mounting These units are suitable for...

Page 122: ...sed Before parallel installation set the battery to limited charge mode Please refer to for detailed operations the software manual To ensure the longest possible life of the lithium ion battery pack...

Page 123: ...thly Environment Keep away from heat sources and avoid direct sunlight Visual inspection In case of breakage leakage or deformation isolate the problematic battery and contact your installer quarterly...

Page 124: ...Step 1 Check the LEDs to determine which part is faulty Step 2 Check the information in case of failure in the monitoring module Step 3 Classify the information DC AC modules batteries control etc St...

Page 125: ...rm disappears replace the module Voltage to low No AC power Check the DC undervoltage alarm point default value is 45V If it is not reasonable please adjust it according to the actual situation Alarm...

Page 126: ...ithin an acceptable range address the interference from the temperature control system When the temperature in the system cabinet returns to the normal range turns off the alarm automatically The temp...

Page 127: ...sensor is defective If yes replace the temperature sensor Battery temperature is too low Battery temperature is set too low alarm point Check if the battery temperature is too low default 0 If yes ad...

Page 128: ...e voltage Default value Maximum value 48 100 40 5 20 100 Parameters for charging multiple modules in parallel Voltage V Capacity Ah Charge voltage limit V Maximum current A nota minimum value Default...

Page 129: ...index 0 1C charging performance Discharge time 600min Standard battery charge 1h within 1h with 0 1C discharge current at 40 5V record the discharge time 0 5C discharge performance Discharge time 115...

Page 130: ...s a green product It should be recycled and not thrown away Recyclage This mark indicates that the product should not be disposed of with other types of waste To prevent potentially hazardous substanc...

Page 131: ...efficiency Environmentally friendly without heavy metals Complete with built in Battery Management System BMS Can use most standard VRLA chargers for this system Low self discharge rate of 2 years be...

Page 132: ...an 20 years Cycle Life Over 3500 cycles at 100 discharge IP class IP31 Casing material Black lacquered steel cabinet Temperature at charging 0 tot 55 C At discharging 20 tot 60 C At storage 20 tot 60...

Page 133: ...22 0 17 423 2 482 6 0 10 40 85 01 0 21 335 5 382 6 0 9 27 67 43 0 26 266 2 303 5 0 8 25 53 49 0 33 211 1 240 7 1 7 35 42 41 0 42 167 4 190 9 2 6 54 33 62 0 53 132 7 151 3 3 5 83 26 67 0 66 105 2 120 0...

Page 134: ...ry must be installed in a suitable place 3 Connect each connector in turn to each of the output ends of the lithium ion battery pack Connect all lithium ion batteries to the positive terminals first t...

Page 135: ...V1 01 135 3 Loosen the screws from the front panel and from the bottom plate 4 Open the front panel and bottom plate 5 Remove the BMS sample leads from the sockets in the following order 4 3 2 1...

Page 136: ...V1 01 136 7 Install the BMS sample cables from the receptacles in the following order 1 2 3 4 7 Install the front panel plate and fastener Reset the battery by pressing the reset button for 6 seconds...

Page 137: ...V1 01 137 APPENDIX...

Page 138: ...V1 01 138...

Page 139: ...V1 01 139 COMPOSITION AND SETTINGS SYSTEMS PB UPS 2 2 24...

Page 140: ...eyes 1 x PB CABR2 35M10 red cale 2m 35mm with M10 cable eyes 1 x PB CABB3 35M10 black cable 3m 35mm with M10 cable eyes 1 x PB 5093300 MEGA fuseholder 1 x PB 5097349 2 MEGA fuses 250A 32V 1 x PB SC12...

Page 141: ...V1 01 141 PB LSC 1 PB SC12 170 PB UPS 2K24...

Page 142: ...V1 01 142...

Page 143: ...V1 01 143 PB UPS 3 5 24...

Page 144: ...e 2m 35mm with M10 cable eyes 1 x PB CABB3 35M10 black cable 3m 35mm with M10 cable eyes 2 x PB CABB0 3 35M10 black cable 0 3m 35mm with M10 cable eyes 1 x PB 5093300 MEGA fuseholder 1 x PB 5097349 2...

Page 145: ...V1 01 145 PB LSC 1 dimensions in mm PB SC12 170 dimensions in mm...

Page 146: ...V1 01 146 PB UPS 3K24 dimensions in mm...

Page 147: ...V1 01 147 PB UPS 5 5 48...

Page 148: ...eyes 1 x PB CABR2 50M10 red cable 2m 50mm with M10 cable eyes 1 x PB CABB3 50M10 black cable 3m 50mm with M10 cable eyes 1 x PB 5073550 ANL fuseholder 1 x PB 5097557 2 ANL fuses 250A 32V 4 x PB SC12...

Page 149: ...V1 01 149 PB LSC 1 dimensions in mm PB SC12 170 dimensions in mm...

Page 150: ...V1 01 150 PB UPS 5K48 dimensions in mm...

Page 151: ...V1 01 151 PB UPS 10 10 48...

Page 152: ...M10 cable eyes 1 x PB CABR2 70M10 red cable 2m 70mm with M10 cable eyes 1 x PB CABB1 70M10 black cable 70mm with M10 cable eyes 1 x PB CABR1 70M10 red cable 70mm with M10 cable eyes 1 x PB 5073550 ANL...

Page 153: ...V1 01 153...

Page 154: ...V1 01 154 PB LSC 2 dimensions in mm B SC12 170 dimensions in mm...

Page 155: ...V1 01 155 PB UPS 5K48 dimensions in mm...

Page 156: ...V1 01 156 PB UPS 15 15 48...

Page 157: ...M10 cable eyes 1 x PB CABR2 95M10 red cable 2m 95mm with M10 cable eyes 2 x PB CABB1 95M10 black cable 95mm with M10 cable eyes 2 x PB CABR1 95M10 red cable 95mm with M10 cable eyes 1 x PB 5073550 ANL...

Page 158: ...V1 01 158...

Page 159: ...V1 01 159 PB LSC 2 dimensions in mm B SC12 170 dimensions in mm...

Page 160: ...V1 01 160 PB UPS 5K48 dimensions in mm...

Page 161: ...V1 01 161 PB UPS 2 2 24 Li...

Page 162: ...yes 1 x PB CABR2 35M10 red cable 2m 35mm with M10 cable eyes 1 x PB CABB3 35M10 black cable 3m 35mm with M10 cable eyes 1 x PB CABB0 3 35M10 black cable 0 3m 35mm with M10 cable eyes 1 x PB 5093300 ME...

Page 163: ...V1 01 163 PB LSC 1 PB Li 12 100D...

Page 164: ...V1 01 164 PB UPS 2K24...

Page 165: ...V1 01 165 PB UPS 3 5 24 Li...

Page 166: ...le 2m 35mm with M10 cable eyes 1 x PB CABB3 35M10 black cable 3m 35mm with M10 cable eyes 1 x PB CABB1 35M10 black cable 1m 35mm with M10 cable eyes 2 x PB CABB0 3 35M10 black cable 0 3m 35mm with M10...

Page 167: ...V1 01 167 PB LSC 1 PB Li 12 100D...

Page 168: ...V1 01 168 PB UPS 2K24...

Page 169: ...V1 01 169 PB UPS 5 5 48 Li...

Page 170: ...1 50M10 red cable 1m 50mm with M10 cable eyes 1 x PB CABR2 50M10 red cable 2m 50mm with M10 cable eyes 1 x PB CABB3 50M10 black cable 3m 50mm with M10 cable eyes 1 x PB 5073550 ANL fuseholder 1 x PB 5...

Page 171: ...V1 01 171 LfeLi48100T dimensions in mm PB LSC Li dimensions in mm...

Page 172: ...V1 01 172 PB UPS 5K48 dimensions in mm...

Page 173: ...V1 01 173 PB UPS 10 10 48 Li...

Page 174: ...1 50M10 red cable 1m 50mm with M10 cable eyes 1 x PB CABB2 70M10 black cable 2m 70mm with M10 cable eyes 2 x PB CABB1 50M10 black cable 1m 50mm with M10 cable eyes 1 x PB 5073550 ANL fuseholder 1 x PB...

Page 175: ...V1 01 175 LfeLi48100T dimensions in mm PB LSC Li dimensions in mm...

Page 176: ...V1 01 176 PB UPS 5K48 dimensions in mm...

Page 177: ...V1 01 177 PB UPS 15 15 48 Li...

Page 178: ...1 50M10 red cable 1m 50mm with M10 cable eyes 1 x PB CABB2 95M10 black cable 2m 95mm with M10 cable eyes 3 x PB CABB1 50M10 black cable 1m 50mm with M10 cable eyes 1 x PB 5073550 ANL fuseholder 1 x PB...

Page 179: ...V1 01 179 LfeLi48100T dimensions in mm PB LSC Li dimensions in mm...

Page 180: ...V1 01 180 PB UPS 5K48 dimensions in mm...

Page 181: ...MEASURES Install this product only in a dry environment To avoid the risk of fire only use correctly dimensioned cables which are suitable for the expected flows in your installation To avoid damage t...

Page 182: ...od The cables for the smaller loads can then be attached to the bolts further away from them to be mounted CHARACTERISTICS High purity tinned copper base plates ensure optimum electrical conductivity...

Page 183: ...V1 01 183 ANL MEGA...

Page 184: ...event excessive mechanical stress on the fuse holder CHARACTERISTICS High purity tinned copper base plates ensure optimum electrical conductivity Optimal corrosion resistance by using stainless steel...

Page 185: ...of the Wi Fi plug 14 with the inverter and insert the plug firmly in touch Secure the Wi Fi plug 14 to the inverter with the screw Check the status of the LED indicator when you see the orange LED li...

Page 186: ...e and download the APP Open the APP tap the Wi Fi Config button to enter this page Tap the Connect Wi Fi Data Logger button on the connected page For Android phones this one is Step not necessary Sele...

Page 187: ...lished tap the Network Setting button Enter the information according to the prompts to complete the network setup Reconnect the Wi Fi Open the APP tap the Register Register button Complete account cr...

Page 188: ...tion Add multiple Dataloggers Note One account can create multiple systems and one system can create multiple data loggers to add If you only have one datalogger you can skip this last step Tap the ne...

Page 189: ...V1 01 189 Finally Note In addition to the SmartClientApp you can also monitor your installations remotely with the mini program WeChat...

Page 190: ...V1 01 190...

Page 191: ...V1 01 191...

Page 192: ...V1 01 192...

Reviews: