background image

 

 

 
 

 
 

 

 
 

USER MANUAL 

 
 

 

 

1000 / 2000 / 3000 VA 

 
 

 

 

 

On-Line UPS 

 
 

 

 

Summary of Contents for E6 LCD 1000 RT

Page 1: ...USER MANUAL 1000 2000 3000 VA On Line UPS ...

Page 2: ...odes Voltage System Configurations 7 3 4 Communication Port Explanation 9 4 INSTALLATION AND OPERATION 10 4 1 Unpacking 10 4 2 Selecting Installation Position 10 4 3 Set up 11 4 4 Operation 14 5 UPS WORKING PRINCIPLE 20 5 1 UPS System Block Diagram 20 6 MAINTENANCE GUIDE 21 6 1 Trouble Shooting 21 6 2 Error Codes and Their Descriptions 22 6 3 Maintenance 22 7 BUNDLE SOFTWARE INSTALLATION GUIDE 23 ...

Page 3: ... any UPS o Install the UPS indoors as it is not designed for installation outdoors To prevent any overheating of the UPS keep all ventilation openings free from obstruction and do not place anything on top of the UPS Keep the UPS rear panel 20 cm away from the wall or other obstructions The battery will discharge naturally if the system is unused for any length of time Install the UPS away from ob...

Page 4: ...nput voltage tolerance from 60V 144V 110V version or 120V 288V 220V version allows under voltage or over voltage correction without unnecessary battery drain and helps extend the battery life span 5 DC start function ensures the start up of UPS even during power outages 6 Revolutionary battery management circuit analyzes battery discharging status to adjust battery cut off point and extend the bat...

Page 5: ...ceptable window 60Vac 79Vac or 120Vac 159Vac Green LED lights up to indicate there is an output available at the Programmable Outlet 1 Programmable Outlet 2 Amber LED lights up to indicate the Bypass Input is normal UPS Fault LED UPS On Alarm Silence UPS OFF Switch Special functions log in out Go to next page Go to previous page or change the setting of the UPS To re confirm the change of UPS Sett...

Page 6: ...n 1 LINE Utility or Bypass Source 2 Battery Low 3 Battery Abnormal 4 UPS Overloading 5 Site Wiring Fault 6 UPS Working in Service Mode 7 OFF UPS Shutoff 8 FAIL UPS Abnormal Lock 9 UPS Flow Chart 10 4 Digits Measurement Display 11 Indicate the item desired to be measured 12 Er05 Battery Weak or Dead 13 Er06 Output Short Circuit 14 Er10 Inverter Over current 15 Er11 UPS Overheat 16 Er12 UPS Output O...

Page 7: ... 2 Real Panel Descriptions 1 USB Port 2 RS232 Port 3 Emergency Power Off EPO Dry Contact Signal inputs 4 Communication Card Options Slot 5 External Battery Connector 6 AC power connection socket 7 AC Outlets 8 Two programmable outlets 9 Utility Input circuit breaker 10 Cooling Fans 11 Output circuit breaker for two outlets 12 Output circuit breaker for two programmable outlets ...

Page 8: ... Sensitivity Select Sensitivity Low Sensitivity High Sensitivity Low Sensitivity High 110V 90V 130V 97V 130V 220V 180V 260V 194V 260V 6 Syn Frequency Window Select 3Hz 1Hz Inverter Freq synchronizing range 7 Com Port Select the Com Port of PC 8 Click on Write to confirm the configuration settings The UPS will beep twice to acknowledge setting is successful 9 Turn off the UPS and unplug input power...

Page 9: ...utlet Turn On After AC Recovered select this option to automatically enable the outlet within the specified time after the utility is restored 4 Outlet Turn Off When Battery Lower than select this option to automatically disable the outlet at the specified remaining battery power capacity during battery mode to shed the less critical loads to prolong battery back up time for the other more critica...

Page 10: ...ows 98 2000 ME NT and XP For other applications such as Novell NetWare UNIX Linux please contact your local dealer for suitable software All the communication ports including optional cards can be active use simultaneously to monitor the UPS status However only 1 communication interface at any one time with the highest priority has the ability to command control the UPS The priority of these commu...

Page 11: ...EC output cables for UPS with IEC sockets only 1 pc of detached AC Input Power Cord for UPS with IEC sockets only 1 set of UPS communication software with RS232 cable 1 set of Tower Rack Accessories Kit as below 4 2 Selecting Installation Position The UPS is heavy Select a location sturdy enough to handle the UPS weight To ensure proper operation and long operating life always position the UPS acc...

Page 12: ...YSTEM 4 rue de la Rigotière 44700 Orvault France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 04 09 AA XX 201 18 11 4 3 Set up Tower Configuration Setup Step 1 Step 2 ...

Page 13: ...PS SYSTEM 4 rue de la Rigotière 44700 Orvault France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 04 09 AA XX 201 18 12 Power Module Battery Module Step 1 Step 2 ...

Page 14: ...rue de la Rigotière 44700 Orvault France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 04 09 AA XX 201 18 13 Rack Mount Configuration Setup Step 1 Step 2 Step 3 Step 4 Step 5 ...

Page 15: ... A to drawing B A B 3 Then the UPS is on Stand By Mode now and it will proceed self test automatically If there is no abnormal message occurred it means the pre start up of the UPS is successful and the charger starts to charge the batteries 4 Press the UPS On Switch for approx 3 seconds then the Buzzer sounds twice If the UPS start up is successful the LCD display changes from drawing B to drawin...

Page 16: ... test Mode The UPS may offer energy to the output in a minute and the LCD display illustrates as drawing I In case of failure in pushing the UPS Off Switch in 10 seconds the UPS will automatically turn off H I Note Ensure the UPS Battery is pre charge for minimum 4 hours by simply connecting the AC power cord to the Utility receptacle Check Measured Values Figures detected by UPS 1 If you would li...

Page 17: ... in sequence Drawing P1 buzzer Drawing Q1 self test Drawing R1 Bypass Voltage Drawing S Output Frequency Synchronized Window Drawing T Inverter Output Voltage Drawing U1 UPS Operation Mode Drawing V Output Voltage Fine Tuning Q1 T Q2 U1 R1 U2 R2 U3 S V 3 Press scroll up key pad you may execute special functions The functions include Buzzer ON as drawing P1 or buzzer OFF as drawing P2 Alarm silence...

Page 18: ...and 1Hz 6 Drawing T means the acceptable Inverter Output Voltage of which voltage is 200V 208V 220V 230V or 240V for 220Vac system or 100V 110V 115V 120V and 127V 7 Drawing U1 U2 and U3 mean the operation modes of the UPS of which alternative is Online fixed 50Hz Output or fixed 60Hz Output 8 Drawing V means the adjustments of the Inverter Output which may be calibrated as 0 1 1 2 2 3 or 3 9 When ...

Page 19: ...urned off the UPS will stop power supply to the outlets and the LCD screen shows as drawing B 2 Turn off the input of the UPS 3 The UPS is turned off completely Status Alarm Buzzer The following table helps to define some of the common UPS statuses with respect to their buzzer beep descriptions Status Definitions Buzzer Beep Descriptions UPS faulty Inverter shutdown All functions inhabited Long Co...

Page 20: ... 4 rue de la Rigotière 44700 Orvault France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 04 09 AA XX 201 18 19 Battery Replacement Step 1 Step 2 Step 3 Step 4 1KVA 2K 3KVA ...

Page 21: ...ter Summery guide to the UPS operating modes against the Utility AC Power Source conditions Utility Conditions UPS Operating Modes LEDs Display indications Utility Normal Rectifier convert AC to DC battery charging Inverter convert DC to AC and supply to loads with clean stable power LEDs remain illuminated Utility Abnormal under or over voltage Absent Rectifier and charger stop operating Battery ...

Page 22: ...provide DC back up Otherwise consult your local dealer right away 2 Disconnect some non critical loads form the UPS output until overload ceases Check if there is any short circuit between cables due to broken cable insulator Replace the cables in necessary 3 Remove any objects obstructing the ventilation louvers Verify if the cooling fans are working properly Contacts your local dealer to replace...

Page 23: ...the battery connectors are fully engaged Allow the battery to recharge if the batter is weak If problem persist after recharging replace the battery If problem persist consult your local dealer for technical assistance 6 2 Error Codes and Their Descriptions 6 3 Maintenance Clean the dust from the ventilation openings and intakes on the rear panel 1 Turn off the UPS and wipe the casing with a damp ...

Page 24: ...nnector of the RS232 USB cable to a dedicated RS232 port of the Computer 3 For optional interface cards please refer to Chapter 8 for more details Note Only RS232 cable is provided with the UPS USB cable is optional 7 2 Software Installation Please refer to the user s manual of the bundled software CD_ROM for installation guide 8 Optional Communication Cards 8 1 R2E 2nd RS 232 card CN1 is for RS23...

Page 25: ... and pin 10 for 5 seconds The capacity of each relay contact is 40Vdc 25mA Installation Position Optional Slot Flexible signal output for N C Normal Close or N O Normal Open contact by shorting pin1 2 or pin2 3 from JP1 5 The shutdown function will be enabled in 1 minute after blackout occurs if the pin1 2 of both CN1 and CN6 are shorted by cap Or the shutdown function can only be enabled by pin9 ...

Page 26: ... Input voltage Input frequency Output voltage Frequency voltage charge level Voltage battery internal Temperature Self diagnostics In mains mode and by software PROTECTION Short circuit off mode immediately Over heating Mains mode Bypass Transfer Battery Mode Automatic shutdown Low battery Alarm and automatic stop EPO Stop immediate Battery Electronic system of management of battery discharge Leak...