KBR multimess F96-...-5
6.6
Hardware inputs and outputs
6.7
Hardware inputs
Voltage
measure-
ment
inputs
U
L1-L
2; U
L2-L3
; U
L3-L1
3 x 5V....
100V
...120V AC (measuring range 1)
3 x 20V...
500V
...600V AC (measuring range 2)
Input impedance
1.2 MOhm (Ph-Ph)
Measuring period
memory
Can be configured using voltage transformers
Current
measuring
input
3 x 0.01A...
1A
...1.2A AC (measuring range 1)
3 x 0.05A...
5A
...6A AC (measuring range 2)
Power
consumption
≤ 0.3VA per input at 6A
Measuring period
memory
Can be configured using current transformers
6.8
Hardware outputs
Signaling
relay for
limit viola-
tions
Number
2 (option)
Contact
floating
Reaction speed
programmable
Switching capacity 250V AC / 2A;
Pulse
output
Output type
proportional to active or reactive energy
3
programmable on the device from 0.001 to
9990 Imp/kWh or kVarh
Optocoupler output 15 mA at max. 35 V; S
0
-compatible
Accuracy class
2
Pulse length
programmable, min. 30 ms
Power supply
external
Interface
(option)
BUS
RS485 for connection to the energy bus; max. 32 devices
Baud rate
38400 fixed at KBR eBus, configurable with Modbus
Addressing
Can be addressed automatically with software or
manually on the device up to address 9999. For
Modbus: 1 to 247 manually on the device.
LAN
IEEE 802.3
speed
10 Mbit / 100 Mbit
Connection
IEEE 802.3 10base-t / 10base-TX, cable CAT5