4.3.5 Wizard setting Voltage Transformer
Primary Voltage:
Corresponds to the primary rated voltage of
the voltage transformer.
Sec. Voltage:
Corresponds to the secondary rated voltage of
the voltage transformer..
The voltage transformer factor is
calculated automatically!
If Power Quality standard for low
voltage network (EN50160-LV &
EN50160-LV-IT) is selected, the
page voltage transformer is
skipped, because the device
can cover the complete range
without transformer settings.
Therefore, no input is necessary,
as no voltage transformer
factor has to be calculated.
4.3.6 Wizard setting Voltage Grid
Reference voltage in low voltage:
Setting the reference voltage in the low
voltage
– TN system as conductor-earth voltage in
volts and in the low voltage
– ITsystem or medium and high voltage as
conductor-conductor voltage in volts.
The non-editable parameters are
calculated automatically.
Setup wizard
Voltage transformer
primary Voltage [V] P-P
20000.00
Setup wizard
Voltage transformer
sekundary Voltage [V] P-P
100.00
Setup wizard
Voltage Grid
Reference voltage [V] P-P
20000
[V] P-N 11547.01
Parameterization