7.4
Storage
7.4.1 Device settings
All device settings and parameter data for storage utilization are stored in the device.
7.4.2 Devices - basic parameters
1*) This function can only be set by means of the PC with optionally available software (e.g. Visual Energy).
7.4.3 Long-term memory
(
multicount 3D6-1-LCD-ES-...
only)
The
multicount 3D6-1-LCD-ES-...
offers the user the long-term memory described in the following section.
7.4.3.1 Load profile memory
The meter has a load profile memory which can record up to a maximum of 4x3840 entries depending on the
number of parameters to be saved (active power periods for HT and LT, consumption and recovery, reactive
power periods for HT and LT, capacitive and inductive) and a measuring period that can be selected by the
user (possible period values 60 / 30 / 15 / 1 minutes).
This means that a period of 60 min. results in a storage duration of 160 days max.
The measuring period can be programmed via the PC using the optionally available software.
b
Note
The parameters cannot be changed by means of the software via the bus as long
as a user is in the configuration menu of the device on location.
Parameters
Stored by user
Measurement voltage, primary
programmable by user from 1 to 9999V
Measurement voltage, secondary
programmable by user from 1 to 500V
Measuring current; transformer primary programmable by user from 0001A … to 9999A
Measuring current (at device input, i.e.
transformer secondary!)
can be selected by user from 1A or 5A
Pulse output type /pulse significance
Pulse length
according to user settings / 0 to 9999 P/kWh
30 to 990 ms
Tariff switching
(
3D6-1-LCD-ES-...
only)
user can select from digital input,
switching via energy bus or times programmed in the device
Synchronization settings
(
3D6-1-LCD-ES-...
only)
setting options: dig. input, bus, tariff switching and internal clock
Bus mode (
3D6-1-LCD-ES-...
only)
choice of Ebus, Modbus rtu or Modbus Ascii
Bus address
(
3D6-1-LCD-ES-...
only)
according to user settings between 0001 and 9999 for Ebus and 1
to 247 for Modbus
Time (
3D6-1-LCD-ES-...
only)
acc. to user settings in hh:mm:ss
Password
(
3D6-1-LCD-ES-...
only)
acc. to user settings
Password is a 4-digit number (leading zeros)
9999 means: Device is not password-protected
Device name (
3D6-1-LCD-ES-...
only)
any name chosen by the user 1*)
Event name
(
3D6-1-LCD-ES-...
only)
an individual designation is assigned to every event
Measuring period
(
3D6-1-LCD-ES-...
only)
1 / 15 / 30 / 60 min. 1*)