Terminal 10 (L1):
11 (L2)
12 (L3)
13 (N)
Measuring input for voltage
Three phase voltage measurement in 4-wire rotary current networks.
Direct measurement is possible in the following networks:
3 x 100V/57,7V AC;3 x 400V/230V AC;
For higher voltages, the unit needs to be connected via a voltage trans-
former.
Terminal 92 (B)
91 (A)
90 (Masse):
Bus connection
For communication at the Energy Bus
multicount 3D6-0-LCD-EP-...: to device parameters
multicount 3D6-1-LCD-ES-...: to connection for power bus
Terminal 34 (+) and 35 (-):
Pulse output
Output of energy-proportional pulses via a digital contact (S
0
interface in
accordance with DIN 43864). Correct polarity is important for this output.
The output signals can be processed by a maximum demand monitor or
a master central process control, for example.
Terminal 36 (+) and 37 (-):
Synchronization input (
multicount 3D6-1-LCD-ES-...
only)
A floating contact, e.g. from the energy supplier for synchronizing the
measuring period, can be connected to this input
Terminal 38 (+) and 39 (-):
Tariff input (
multicount 3D6-1-LCD-ES-...
only)
A floating contact, e.g. from the energy supplier for switching from high to
low tariff, can be connected to this input.n.