Connection diagram
4.3
Terminal assignment
Terminal 1 (L) / 2 (N) and PE: Connection power supply
A control voltage is required to supply the device with power. The device
can be operated with a voltage from 85V to 265V.
Terminal 20 (k1) and 21 (l1):
22 (k2) and 23 (l2)
24 (k3) and 25 (l3)
Measuring inputs for current
The measuring inputs for current must be connected via current
transformers x/1A AC or x/5A AC.
When connecting transformers, pay attention to the energy flow direction
and to the correct assignment of measuring voltage inputs to current
transformers.