8.4.4 Electrical wiring percautions
a. On-site wiring, parts and materials must comply with the local
and national regulations as well as relevant national electrical
standards.
National
standard
Fig. 8-8-1 Electrical wiring precaution (a)
b. Copper core wires must be used
Copper core wires
Fig. 8-8-2 Electrical wiring precaution (b)
c. It is advisable to use 3-core shielded cables for uint to
minimize interference. Do not use the unshielded multicore
conductor cables.
Fig. 8-8-3 Electrical wiring precaution (c)
d. Power wiring must be entrusted to professionals with
electrician qualification.
Fig. 8-8-4 Electrical wiring precaution (d)
8.4.5 Power supply specification
Table 8-5
Item
Model
Outdoor power supply
Power supply
Manual switch
Fuse
Wiring
65KW
380-415V/3N~50Hz
100A
63A
16mm
2
X5 (<20m)
110KW
380-415V/3N~50Hz
200A
150A
50mm
2
X5 (<20m)
• See the table above for power wire diameter and length when the voltage drop at the power wiring point is within 2%. If
the wire length exceeds the value specified in the table or the voltage drop is beyond the limit, the power wire diameter
should be larger in accordance with the relevant regulations.