38
12 APPLICABLE MODELS AND MAIN PARAMETERS
Table 12-1
Model
65KW
110KW
Cooling capacity
kW
57.0
100.0
Heating capacity
kW
65.0
110.0
Standard cooling input
kW
19.0
32.8
Cooling rated current
A
29.3
50.6
Standard heating input
kW
18.3
29.9
Heating rated current
A
28.2
46.1
Power supply
380-415V 3N~ 50Hz
Operation control
Control of wired controller, auto startup, running state display, failure alert etc.
Safety device
High or low pressure switch, freeze-proof device, water flow volume controller, Overcurrent device,
power phase sequence device etc.
Refrigerant
Type
R32
Chargeing volume kg
9.0
15.5
Water pipe system
Water flow volume m
3
/h
9.8
17.2
Hydraulic resistance lose kPa
44
39
Water side heat exchanger
Plate heat exchanger
Max. pressure MPa
1.0
Min. pressure MPa
0.15
Inlet and outlet pipe dia.
DN50
DN65
Air side heat exchanger
Type
Fin coil model
Air flow volume m
3
/h
22000
32500
Outline dimension N.W.
of the unit
L mm
2000
2220
W mm
960
1135
H mm
1770
2300
Net Weight
kg
440
670
Operation Weight
kg
450
700
Packing dimension
L × W × H mm
2085×1030×1890
2250×1180×2445
Summary of Contents for KEM-HT-65 DRS5
Page 56: ...16127100001537 V B ...
Page 57: ......