Kaysun COMPAK KHP-15/190 ACS2 Owners & Installation Manual Download Page 11

Table

.

3-2

3.3.1   Specifications of Power Supply 

4

30/25

30 mA 

 ≤

0.1sec

Creepage Breaker

Earth Cord

 

(mm

2

)

Manual Switch(A) Capcity/Fuse

(

A

)

Model Name

Power Supply

MIin. Diameter of Power

Supply Cord

 

(mm

2

)

220-240V

50Hz

KHP-15/190 ACS2

  4

Please choose the power cord according to above table, and 

it should comply with local electric standard.

The power cord model, recommanded power cord mode is 

H05RN-F.

When wiring the power supply, please add additional insulation 

sheath at the place without rubber insulation layer. 

3.3  Electric Connection

3.3.2 Switch setting 

Fig.3-12

Fig.3-13

Fig.3-11

3.3.3  Electric leakage protector

L

N

GND

Power Cable with 

Creepage Breaker

Creepage Protector

Power Supply

 3.4.1 Location

The flooring beneath the water heater must be able to support

 the weight of the unit when filled with water (more than 286kg).

Located indoors (such as a basement or garage) and in a 

vertical position. Sheltered from freezing temperatures.

Provisions made to shelter the area from water damage. 

Metal drain pan installed and piped to an adequate drain.

Sufficient room to service the water heater.

Sufficient air for the heat pump to function,

the water heater must be located in a space >15m³, and must 

have unrestricted air flow.

3.4 Installation checklist

Fig.3-14

Select the model by dialing S1 on the motherboard

1 2 3 4

ON

S1

3.3.4  When Modbus and remote switch are optional:

1) After inserting the weak current connection cable group, secure

the weak current connection cable group using the two cable ties

on the right of the junction box. 

see 

Fig.3-13

2) The mating terminal should be placed on the top to prevent it from

being wetted by the condensate in the drain pan.

3) Route the weak-current cable group and power cable through the

two holes reserved on the junction box cover.

see 

Fig.3-14

4) MODBUS and remote switch functions require the purchase of

connecting wires. The length of each wire is 6m. Select and

purchase the corresponding number of wires according to the demand.

Set the electric leakage protector according 

to the relevantelectric technical standards 

of the state

.

The power cord and the signal cord shall be 

laid out neatly and properly without mutual 

interference or contacting the connection 

pipe or valve.

After wire connection, check it again and 

make sure the correctness before power on.

CAUTION

The power supply should be an independent 

circuit with rated voltage.
Power supply circuit should be earthed 

effectively.

The wiring must be performed by 

professional technicians in accordance 

with national wiring regulations and this 

circuit diagram.

An all-pole disconnection device which 

has at least 3mm separation distance in 

all pole and a residual current device

(RCD)with the rating of above 10mA shall 

be incorporated in the fixed wiring 

according to the national rule.

WARNING

The unit must be installed with an Creepage 

Breaker near the power supply and must be 

effectively earthed.

8

Summary of Contents for COMPAK KHP-15/190 ACS2

Page 1: ...y much for purchasing our product Before using your unit please read this manual carefully and keep it for future reference COMPAK KHP 15 190 ACS2 Type Air source Heat Pump Water Heater OWNER S INSTAL...

Page 2: ...ole disconnection device which has at least 3mm separation distance in all pole and a residual current device RCD with the rating not exceeding 30mA shall be incorporated in the fixed wiring according...

Page 3: ...re of this manual When ordering repair parts please always give the following information 1 Model serial and product number 2 Parts name Front Cover Electronic Control Box Compressor Display Cover Ele...

Page 4: ...ker must be installed adjacent to the power supply Do not remove cover or deface any permanent instructions lables or the data label from either the outside of the unit or inside of unit panels Ask qu...

Page 5: ...ngers such as water electricity and gas Before wiring pipes Before installation check whether the user s power supply meets the electrical installation requirements of unit including reliable groundin...

Page 6: ...strong wind The base surface should be flat surface should be inclined no more than 2 and able to bear the weight of the unit and suitable for installing the unit without increasing noise or vibratio...

Page 7: ...ir flow As an example a room that has an 2 5 tall ceiling and is 3 meter long by 2 meter wide would contain 15m 2 5 Unit outline dimension unit mm 4 2 3 Maintenance space requirements unit mm Fig 2 1...

Page 8: ...o not dismantle the PT Valve Do not block off the drainage pipe It will cause explosion and injury if do not comply with the above instruction EXPLOSION Water inlet or outlet pipes The spec of the wat...

Page 9: ...connects to duct air outlet without duct 2 2 5 5 2 2 5 5 Straight line length m Bent pressure drop Pa Bent s qty Straight line pressure drop Pa m Duct Description Duct Round duct Rectangle duct 160 1...

Page 10: ...e pay attention to the drainage work we sugest to wrap the thermal insulated layer around ouside of the duct For the case of unit with duct the duct total length should be no more than 5m or the maxim...

Page 11: ...itch are optional 1 After inserting the weak current connection cable group secure the weak current connection cable group using the two cable ties on the right of the junction box see Fig 3 13 2 The...

Page 12: ...free of leaks Unit completely filled with water Water temperature limit valve or mixer tap recommanded installed per manufacturer s instructions Condensate Drain Line Installation Must be located wit...

Page 13: ...stop heat pump activate E heater to continually heat water to the target temperature If manually activate the E heater running when heat pump running E heater and heat pump will work together until th...

Page 14: ...ure is higher than 85 the TCO will automatically shut off the power of compressor and E heater After that it needs to be reset manually 1 2 3 4 4 2 4 Query function For the convenience of maintenance...

Page 15: ...htened otherwise will be extinguished E heat will be lightened when E heat is running otherwise will be extinguished Solar will be lightened when the machine is connected to the solar signal or connec...

Page 16: ...Adjust vacation days 1 360 days Switch to HYBRID mode Use this key to switch mode MODE CLOCK TIMER ON OFF DISINFECT No Icon Description 5 CLOCK CLOCK Press this button to enter the clock setting SET...

Page 17: ...corresponding value will decrease by pushing When setting temperature press more than 1s temperature value will be decreased continuously When Setting clock timer press more than 1s Clock timer value...

Page 18: ...con to add home appliance to your Comfort Home account Connected to the network Follow the insturctions in the app to set up the WiFi connection If the network connection fails please refer to the App...

Page 19: ...s not have electric heating function the heat pump available running ambient range is 7 43 if ambient tempera ture is out of range system will show above mentioned signal to let user notice it Q Why s...

Page 20: ...ture protection Tp 115 Protection active Tp 90 Protection inactive Maybe because of system blocked air or water or less refrigerant leakage in system after repair water temperature sensor malfunction...

Page 21: ...time please Shut off the power supply Release all the water in water tank and the pipeline and close all the valves Check the inner components regularly 7 2 Recommended regular maintenance table 7 1 M...

Page 22: ...d around outside of Aluminum microchannel heat exchanger Hydrophilic aluminum fin inner groove copper tube 28W 560 1787mm 3150W Max operating pressure 1 0MPa Water tank cap Water heating cap 1500W 390...

Page 23: ...is installed at least every 24 months 2 For equipment that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO2 equivalent or more but of less than 500 tonnes of CO2 equipment at le...

Page 24: ......

Reviews: