5 Commissioning
5.5.4 Analogue voltage output 0 – 10 v
Voltage outputs may be assigned to process values in the “mode” section of the
output menu. The outputs can be programmed and scaled within the menu struc-
ture.
Wiring
Electrical
characterist-
ics
Galvanically isolated from main electronics and from other I/O's.
Range 0...10 V.
RLoad=1000 ohm.
Resolution: 16 bit, accuracy: 0.1% of MV.
5.5.5 Analogue frequency output (passive)
Frequency outputs may be assigned to process values in the “mode” section of the
output menu. The outputs can be programmed and scaled within the menu struc-
ture.
Wiring
Electrical
characterist-
ics
Galvanically isolated from main electronics and from other I/O's.
Open-collector: 2...10000 Hz.
U=24 V, Imax=4 mA.
5.5.6 Digital open collector output
Open-Collector outputs may be assigned to process values in the “mode” section of
the output menu. The outputs are configured using the menu structure.
The totaliser function is enabled and controlled using the menu structure
Wiring
Electrical
characterist-
ics
Galvanically isolated from main electronics and from other I/O's.
Totaliser pulse, value 0.01...1000/unit.
Active high and active low available.
Width 1...990 ms.
U=24 V, Imax=4 mA.
35