background image

8/07

 

 
2.3. SAFETY DISTANCES AND SAFEGUARDS  
Failure to observe safety distances causes a risk of fire! 

Sauna heaters are classified as hot units with a maximum surface temperature of 350

o

C (662°F). The 

minimum distance from the rear and the sides of the heater to any combustible material or 
surface is 500 mm (20”); from the front of the heater 1,000 mm (40”), and from the top of the 
heater 1,200 mm (48”). 

A 50% reduction in the safety distances is achieved with a single protective sheet and a 75% reduction 

with a double sheet. Such a sheet may consist of 1 mm (3/64”) thick metal sheet or 7 mm (9/32”) 
thick fiber-reinforced cement board

 

(no paper-faced or similar gypsum board). A ventilation gap 

of  30  mm  (1 

¼

”)  must  be  left  between  the  wall  and  the  protective  sheeting.  Additionally,  the 

sheeting must be clear of the floor and ceiling. With heaters fitted with a hot water tank, the safety 
distance to combustible material on the side of the tank is 150 mm (6”). If the floor of the sauna in 
front of the heater is made of combustible material, the area to be protected should extend 100 
mm  to  both  sides  of  the  fire  door  and  to  a  minimum  distance  of  400  mm  (16”)  forward.  The 
protective sheeting must consist of a metal sheet with a minimum thickness of 1 mm. See also 
section 2.4. 

A 50 mm (2”) clearance to a brick wall is required on the sides and in the rear of the heater. 
The safety distances of the connecting pipes between the heater and the chimney are 1,000 mm (40”) 

in  the  lateral  direction  and  1,200  mm  (48”)  in  the  vertical  direction.  Safety  distances  can  be 
reduced using similar protective sheeting as with the heater itself. The minimum safety distance 
of Kastor chimneys to combustible materials is 100 mm (4”), provided that the insulated part of 
the chimney extends down to a height of 400 mm (16”) below the ceiling.  

If you are uncertain, consult the local building authorities. 

Heaters  with  an  extended  fire  door  section  may  only  be  installed  through  a  wall  made  of 

incombustible material (brick, concrete, etc.).

 Then, the incombustible material must enclose 

the  extended  fire  door  as  shown  in  Fig.  5.  If  the  floor  in  front  of  the  fire  door  is  made  of 
combustible material, the area to be protected should extend 100 mm (4”) to both sides of the fire 
door and to a minimum distance of 400 mm (16”) forward. The protective sheeting must consist 
of a metal sheet with a minimum thickness of 1 mm (3/64”). See also section 2.4.  

 
2.4. INSTALLATION BASE

 

Install the sauna heater on a level, firm and stable 

fire-insulated base

, The front feet of the heater 

include openings for adjusting screws that can be used to level the heater on a sloping floor. The 
screws are found in the accessory bag inside the heater. Insert the screws and level the heater. 
The best base is made of cast concrete. 

Installation on a tiled floor is not recommended 

because damp proof courses and tile adhesives contain materials sensitive to heat. Please note 
that light-coloured wooden floors are easily soiled by the ash and other impurities associated with 
wood-fired heaters. 

With proper fire insulation, the heater can also be installed on a wooden floor. Acceptable insulation is 

usually  provided  by  a  60  mm  (2  7/16”)  thick  cast  concrete  slab  with  a  smooth  finish  and  slight 
forward slope (ensure moisture removal). The fire insulation on the floor must extend a distance 
of 400 mm (16”) beyond the front of the heater, 250 mm (10”) on both sides and 250 mm (10”) in 
the rear, or up to an insulated wall on the side and in the rear. 

– Heaters with an extended fire door section

 

The floor of the steam room and the room in which the fire door is located must be at the same level. 

Alternatively, the floor of the room with the fire door may be lower that that of the steam room but 

never higher!

 

The heater, the extended fire door section included, is installed on a level, firm and stable fire-

insulated base, preferably made of cast concrete

If the floor of the room in which the fire 

door is located is made of a combustible material

, there must be a layer of incombustible fire 

insulation  with  a  minimum  thickness  of  60  mm  (2  7/16”)  underneath  the  extended  fire  door 
section  (such  as  cast  concrete  or  brickwork).  As  far  as  fire  insulation  on  the  fire  door  side  is 
concerned, also consider the instructions given in section 2.3.  

With proper fire insulation, a heater with an extended fire door section can also be installed on 

a  wooden  floor. 

However,  the  partitioning  wall  must  then  be  made  of  incombustible  material 

(brickwork, concrete, etc.). Both for the steam room and the room where the fire door is located, 
acceptable insulation is usually provided by a 60 mm (2 7/16”) thick cast concrete slab (ensure 

4211-60  

Kastor K-007, KL16VE 

3/25/11 

 

 

Rev. 1 

Summary of Contents for K-007

Page 1: ...chosen a KASTOR product for your fireplace Fireplace hearts from KASTOR are renowned for their high quality and long life SAVE THESE INSTRUCTIONS After installation these instructions must be given to...

Page 2: ...over or the scoop can cause the water to boil over abruptly 2 INSTALLATION 2 1 PREPARATIONS x Place the sauna heater without stones and water tank or with the water tank filled with water if applicabl...

Page 3: ...to a minimum distance of 400 mm 16 forward The protective sheeting must consist of a metal sheet with a minimum thickness of 1 mm 3 64 See also section 2 4 2 4 INSTALLATION BASE Install the sauna hea...

Page 4: ...ey Be sure to select the right size of chimney with due regard to heater model chimney height ambient conditions etc To ensure optimum performance always use a flue damper x First insert the heater s...

Page 5: ...t seal 1 onto the threaded section of the tap x Insert the tap into the hole in the heater mantle x Insert seal 2 onto the threaded section of the tap inside the mantle x Lift the water tank in positi...

Page 6: ...ways use natural untreated wood preferably solid birch or alder cut to a length of one third of a meter 12 Wet or rotten wood does not produce much heat Never burn impregnated wood wood containing nai...

Page 7: ...e sustained at the right level for a long time When going to the sauna you can add a couple of logs if necessary 3 8 CLEANING THE HEATER REMOVAL OF ASH AND CHIMNEY SWEEPING To wash the exterior of the...

Page 8: ...capacity see selection guide Keep the vent open to let excessive heat escape to allow the stones to heat up in the process In this way the time required for heating is slightly longer 21 Is the heati...

Page 9: ...8 07 4211 60 Kastor K 007 KL16VE 9 3 25 11 Rev 1...

Page 10: ...8 07 4211 60 Kastor K 007 KL16VE 10 3 25 11 Rev 1...

Page 11: ...8 07 4211 60 Kastor K 007 KL16VE 11 3 25 11 Rev 1...

Page 12: ...8 07 4211 60 Kastor K 007 KL16VE 12 3 25 11 Rev 1...

Page 13: ...n insulated connecting pipe from above when connecting to combustible material from connecting pipe surface to the side 1000mm 40 upwards 1200mm 48 B The stove s distance from combustible material to...

Page 14: ...8 07 4211 60 Kastor K 007 KL16VE 14 3 25 11 Rev 1...

Reviews: