VIII. Troubleshooting

Fault Alarm and Troubleshooting

When the inverter is abnormal, protection function acts: LED displays fault code and the content, fault relay acts,
the inverter stops output and the motor coasts to stop. Mini series inverter’s fault contents and troubleshooting
is shown in Table 7-1. After fault alarm occurs, fault phenomenon should be recorded in detail, the fault should
be processed according to Table 7-1. When in need of technical assistance, please contact your supplier.

Fault

code

Type of faults

Possible fault reasons

Troubleshooting

E-01

Acc over current

Acc time is too short

Adjust acc time

V/F curve setup is not suitable

Adjust V/F curve

Restart the motor in running

Setup start mode as speed tracking restart

Torque boost setup is too big

Adjust torque boost or set as auto mode

Inverter capacity is too low

Select inverter with proper capacity

E-02

Dec over current

Dec time is too short

Adjust Dec time

Potential load or load inertia is too big

Add suitable braking device

Inverter capacity is too low

Select inverter with proper capacity

E-03

Over current at
constant speed
running

Load mutation

Check load

Acc or Dec time is too short

Adjust Acc or Dec time

Input voltage abnormal

Check input power supply

Load abnormal

check load

Inverter capacity is too low

Select inverter with proper capacity

E-04

Acc overvoltage

Input voltage abnormal

Check input power supply

Acc time is too short

Adjust Acc time

Restart the motor in running

Setup start mode as speed tracking restart

E-05

Dec
overvoltage

Dec time is too short

Adjust the Dec time

Potential load or load inertia is too big

Add suitable braking device

E-06

Overvoltage

at

constant speed
running

Input voltage abnormal

Check input power supply

Acc or Dec time is too short

Adjust the Acc or Dec time

Abnormal change of input voltage

Mount input reactor

Load inertia is too big

Add suitable braking device

E-07

Overvoltage

of

control

power

supply

Input voltage abnormal

Check input power supply

E-08

Inverter overheat

Air duct obstruction

Clean air duct

Environment temperature is too high

Improve the ventilation or decrease the
carrier frequency

Summary of Contents for KD3000 Series

Page 1: ...KD3000 Series Mini Inverter Simple Manual 6w 200w Mini Inverter Green Intelligent Energy Saving Shenzhen Karda Electric Co Ltd www szkarda com...

Page 2: ...the input power is off Be sure to install the terminal cover before turning on the power When removing the cover be sure to turn off the power Grounding terminal must be grounded reliably Do not touc...

Page 3: ...put Terminals U V W 220V 3 Phase output Terminals Grounding V Basic Wiring Diagram Sort Terminal Name Function Description Specification Communi cation 485 RS485 communication port RS485 differential...

Page 4: ...rogramming see terminal function parameters P4 group input terminal functions Common port COM X2 Multifunctional input terminal 2 X3 Multifunctional input terminal 3 Power source 10V 10Vpower source S...

Page 5: ...on control panel single display valid 1 key on control panel single display valid Panel digital potentiometer key on control panel double display valid 2 Digital setting 1 control panel given 3 Digit...

Page 6: ...80 0 Acc Dec time P0 14 P0 15 90 0 1 60 0 P0 16 Acc Dec time unit 0 Second 1 Minute 0 0 P0 17 Acc time 1 0 1 6000 0 0 1 20 0 P0 18 Dec time 1 0 1 6000 0 0 1 20 0 P0 19 Upper limit freq Lower limit fre...

Page 7: ...start from start freq 2 Track speed then start 1 0 P2 01 Start freq 0 40 20 00Hz 0 01Hz 0 50Hz P2 02 Start freq running duration 0 0 30 0s 0 1s 0 0s P2 03 DC brake current as start 0 15 1 0 P2 04 DC...

Page 8: ...7 Acc Dec time terminal 2 8 Acc Dec time terminal 3 9 3 wire control 10 Free stop input FRS 11 External stop command 12 Stopping DC brake input command DB 13 Inverter running prohibited 14 Freq increa...

Page 9: ...ction parameter Func Code Name Range Min Unit Factory default Modify P6 00 Last fault record Last fault record 1 0 P6 01 Output freq in last fault Output freq in last fault 0 01Hz 0 P6 02 Set freq in...

Page 10: ...too big Add suitable braking device Inverter capacity is too low Select inverter with proper capacity E 03 Over current at constant speed running Load mutation Check load Acc or Dec time is too short...

Page 11: ...ns voltage General motor runs at low speed with heavy load for long term Use a special motor for long term running Wrong setting of motor overload protection factor Set the factor right Motor chocked...

Page 12: ...ll input power source filter DSP read write error Reset or contact supplier E 17 EP2PPROM error Read write error of control parameter press key to reset or install input power source filter E 18 Motor...

Page 13: ...of fault and clearing otherwise the inverter may be damaged 2 If it can t be reseted or fault occurs again after reset please check the cause of fault continuous reset may damage inverter 3 Reset the...

Reviews: