English 5.906-548.0 Rev. 00 (04/12)
49
6.1.5 Set up the switching off process
Function
adjustment
Display
Significance
30 °C
ON30MIN
Behaviour of device after 30 min-
utes of continuous operation.
The setting will be saved.
Switching using SET.
The device switches off after 30 min-
utes of continuous operation
Factory setting
The device does not switch off after 30
minutes of continuous operation
33 °C
OFF30MIN
Behaviour of device after 30 min-
utes of continuous standby oper-
ation.
The setting will be saved.
Switching using SET.
The device switches off after 30 min-
utes of standby operation
The heater in the boiler also shuts off.
The device does not switch off after 30
minutes of standby operation (factory
setting).
6.1.6 Set up the leakage behaviour
Function
adjustment
Display
Significance
35 °C
LECKAGEONOFF
Switching using SET.
The device switches off after 10 short
startups of the pump (factory setting).
The device does not switch off after 10
short startups of the pump.
6.1.7 Check the indicator lamps
Function
adjustment
Display
Significance
38 °C
LEDTEST
The two light patterns are shown alter-
natingly to control the function of the
LEDs in the indicator lamps.