Karassn KS-858G User Manual Download Page 11

No stored phone numbers by default

Directive 15-19: Set zone list to dial corresponding telephone number when alarming

             How to set self-test report function
In installer program state

st

    Press 

15

+

OK 

 +

appointed zone no.

+

OK 

to set appointed zones to dial the 1  

 phone number.

nd

    Press 

16

+

OK 

 +

appointed zone no.

+

OK 

to set appointed zones to dial the 2  alarm phone number

rd

    Press 

17

+

OK 

 +

appointed zone no.

+

OK 

to set appointed zones to dial the 3  alarm phone number 

th

    Press 

18

+

OK 

 +

appointed zone no.

+

OK 

to set appointed zones to dial the 4  alarm phone number 

th

    Press 

19

+

OK 

 +

appointed zone no.

+

OK 

to set appointed zones to dial the 5  alarm phone number

Note: The alarm host can set inform whether or not for Arm/Disarm and malfunction inspection. Code 9 is for Arm/Disarm.
 Code 10 is for malfunction inspection (malfunction inspection includes backup power lower of alarm host/detector, AC 
power cut off). Input

SET 0

for 10.  It will show on LCD.

For instance, you want to set zone 1, 3, 5, 7 to dial the first alarm phone number when there are alarm occur. You can 
set as follows:

alarm

 

Picture 9

In installer program state
Press 

15

+

OK 

 +

1, 3, 5, 7

+

OK 

LCD display will show as below

If you want to set 2, 4, 6, 8 zones. When those zones occurs alarm or Armed/Disarmed and panel malfunction inspection 
report, it will dial the second alarm phone number automatically.
In installer program state
Press 

16

+

OK 

 +

2, 4, 6, 8, 9, SET 0 

+

OK 

LCD display will show as below

 

Picture 10

In Ex-factory state, all zones dial all phone numbers except for Arm/Disarm and malfunction inspection.

Directive 21: Set telephone communication Protocol 

In installer program state
Press

21

+

OK 

 +

x x x x x

+

OK 

, x= (0, 1,2,3,4) means communication code, 0 for closed, 1 for GSM  

CONTACT ID protocol alarm, 2 for PSTN CONTACT ID protocol alarm, 3 for PSTN audio alarm, 4 for GSM audio alarm.
 x x x x x is protocols for 5 alarm phone numbers.
For instance, the first and the second alarm number for PSTN CONTACT ID protocol alarm, the third, forth and fifth 
alarm number for GSM audio alarm.
In installer program state
Press

21

+

OK 

 +

2 2 4 4 4

+

OK 

LCD display will show as below

 

Picture 11

Noted: All 

 phone numbers are set to be PSTN audio alarm by default

Directive 22: Set dialing times

In installer program state,
Press

22

+

OK 

 +

x

+

OK 

 , x= (1-9)

Note: The dialing times is for alarm phone which was not received successfully 
In Ex-factory state, it has been set to be 5 times.

Directive 23: Set ring times

In installer program state
Press

23

+

OK 

 +

x x

+

OK 

, x x= (05-15)

Note: alarm host receives a remote call, when the ring times arrive, the panel will enter program state , then you can 
set remotely.In Ex-factory state, it has been set to be 8 times.

alarm

-9-

Summary of Contents for KS-858G

Page 1: ...PSTN GSM GPRS Alarm System User Manual 1 2 3 4 5 6 7 8 9 0 RUN AC PWR ARM EMC Z1 Z2 Z3 Z4 Z5 Z6 27 Z8 ARM SEY OK RESET WELCOME...

Page 2: ...1 Directive 35 Set linkage alarm duration for appointed zones 12 Directive 36 Set the first group of Arm Disarm timer for zone list 12 Directive 37 Set the second group of Arm Disarm timer for zone li...

Page 3: ...re 8 wired zones and 8 wireless zones altogether and they share with the zone number 2 6 8 sub zones can be programmed independently And the zone list can be set freely in each sub zone 8 r emote cont...

Page 4: ...24 hours or more in standby time And it reports when power lower to avoid battery damaging it adopts limited current discharge protection circuit 2 22 Remote control arm and disarm linkage active sire...

Page 5: ...nearby it also should be near to telephone line and within the detector defense zone Siren or trumpet should be set in the best place Emergency button should be set in the most convince place When in...

Page 6: ...e inserted is too long If more than two lines should be connected to the same end then the bared line should be twisted firmly then insert them into the hole After that screw the screw cap firmly to b...

Page 7: ...in some zones NC is normal close end And NO is normal open end COM is common end Their interfaces can connect with 1A120V AC 24V DC If the power of being controlled equipment over interface loads the...

Page 8: ...nt cap opening short circuit end should be put to outer case concatenate both ani tamper switches and then connect the line end with TAMPER C interface 4 3 System Debugging Firstly check if all lines...

Page 9: ...press Reset key then enter wanted directives 5 2 Program Instruction Enter program state Panel is in standby state or repeatedly press Reset key to set panel in standby state Press SET key the panel...

Page 10: ...r instance you want to delete the 8th user code In installer or master program state Press 08 OK OK Note 3 1 8 user s codes and 1 8 remote controllers are defined to be 1 8 users and different users c...

Page 11: ...rmed Disarmed and panel malfunction inspection report it will dial the second alarm phone number automatically In installer program state Press 16 OK 2 4 6 8 9 SET 0 OK LCD display will show as below...

Page 12: ...tate Press 30 OK xxxxxxxx OK x is zone attribute of each zone 8 x is for 8 zones X value scale you can see attribute table below Note 1 Zone attribute depends on detector types 2 Fire alarm Gas alarm...

Page 13: ...s by default Directive 33 Set Alarm delay Arm delay for appointed zones In installer program state Press 33 OK Alarm delay time Arm delay time appointed zones 1 8 OK Alarm delay time range 00 99 secon...

Page 14: ...alarms Linkage alarm siren duration is 30 minutes In install program state press 35 OK 30 2 4 6 8 9 OK The screen will show as below Picture 14 Linkage alarm duration 20 minutes for all zones by defa...

Page 15: ...tition Press 44 OK appointed zone no OK for the 4th partition Press 45 OK appointed zone no OK for the 5th partition Press 46 OK appointed zone no OK for the 6th partition Press 47 OK appointed zone n...

Page 16: ...3 Enable disable bypass reporting function In installer program state Press 53 OK x OK x 0 1 0 means disable bypass reporting function 1 means enable bypass reporting function and bypass recovery repo...

Page 17: ...host will recognize automatically to see if this code has been learned if this remote controller has been learned then the alarm host will refuse to learn this code and it will make a Di sound 1 Afte...

Page 18: ...he 2nd sensor Press 3 OK OK to delete the 3rd sensor Press 72 OK to enter the 2nd zone register Press 1 OK OK to delete the 1st sensor Press 2 OK OK to delete the 2nd sensor Press 3 OK OK to delete th...

Page 19: ...2345678 35 2012345678 36 Set the 1st timer for Arm Disarm No 37 Set 2nd timer for Arm Disarm No 38 Correct Date and Time 41 12345678 42 12345678 43 12345678 44 12345678 alarm Set delete the 1st alarm...

Page 20: ...disable GPRS 1 57 Set and query IP address of master server 58 Set and query the master server port number 9022 59 Set and query heartbreak time 55 seconds 60 Register delete remote controller No 69 D...

Page 21: ...ion or failure Slow flashing GSM initialization succeeded but network server was not logged in Indicator on Successful login to the network server Arm indicator the indicator is on for arm and off for...

Page 22: ...ck to normal TEL Error Telephone line failure TEL Back Telephone line come back to normal MBAT Low Alarm host battery power low MBAT Back alarm host battery come back to normal TEL ErZx Low x 1 8 Zx F...

Page 23: ...but the system also send out the alarm information through telephone to ask for help at the same time 6 3 Arm Disarm 1 The remote controller programmed to arm disarm for different partitions Press ke...

Page 24: ...bute in Intrude Alarm or Perimeter alarm they won t activate until alarm host in Arm state So don t forget to ARM the alarm system before you leave the place 2 Emergency Alarm Press key for emergency...

Page 25: ...d then hang up One sound indicator Du means the code is correct Then you are able to enter directive you wanted If no operation beyond 30 seconds the phone will be hung up If incorrect code was entere...

Page 26: ...nection function enabled directive 56 enabled by default 7 1 The alarm host installs the SIM card correctly 7 2 Download APP as below 7 3 Open the APP to register an account It can be registered by em...

Page 27: ...sfully 7 5 Alarm host operation instructions Modifiable host name Share device to other APP account Indicate online offline Away arm System settings of alarm host Note Each alarm host can only be adde...

Page 28: ...and alarm host in open area 400m Working Environment Temperature 0 55 Humidity 10 80 8 2 Wireless Remote Controller Voltage 12V 27A Standby Current 5uA Emit Power 10mw Emit Frequency 433 92MHz 9 Opera...

Page 29: ...alarm when powered on or Armed 1 The wired sensor connected is incorrect or connect badly Check the power cable to see if the plus terminal and signal terminal are connected correctly Or see if termin...

Page 30: ...ed environment temperature when the temperature of protected area reach to 32 40 the performance of infrared detector detect distance will reduce So we suggest you to check its working performance car...

Page 31: ...V1 0 P M...

Reviews: