DN1315-1007
4
KT-300 Door Controller Installation Manual
Technical Specifications
Specification
Description
AC Power Imput
120/16VAC, 40VA, class 2 transformer (North America)
230/16VAC, 100VA, fused transformer (Europe)
Battery Back-up
1battery 12VDC, 7Ah, supervised, provides up to 12 hours of operation, Kantech BD7-12 battery
tested for 4 hours standby for UL294
Operating
Temperatures
From 2°C to 40°C (35°F to 110°F)
Cabinet Dimensions
(H-W-D)
29.9 cm x 28.8 cm x 7.7 cm (11-3/4” x 11-3/8” x 3”) EMT 1.9 cm (3/4”) (North American model)
33.5 cm x 35 cm x 8 cm (13” x 13-3/4” x 3”) (European model)
Cabinet Weight
2.4 kg (5.4 lbs) North American model
5.6 kg (12.4 lbs) European model
PCB Dimension
18.3 cm x 12.18 cm x 5.20 cm (7-1/4” x 4-3/4” x 2-1/16”)
Reader Types
Wiegand, proximity, bar code, magnetic, integrated keypad and others
Reader Power Output
12 VDC and 5VDC @ 175mA max, protected and supervised
Monitored Points
8 monitored points, NO/NC, w/without EOL’s (expandable to 16), use UL recognized tamper
switch on cabinet housing to conform with UL 294
Points Maximum Wiring
AWG #22 - 600 meters (2,000 feet)
Door Strike Power
12 V DC, 250mA max each, supervised
Auxiliary Outputs
4 outputs, 25mA max each, open collector
Relay Controlled Output
2-relay controlled outputs, 25mA max each. Open collector to ground (use form “C” relays
Kantech #KT-RM1 if needed)
Auxiliary Power Output
11.5 to 13.85 VDC @ 175mA max, protected and supervised
Communication Ports
RS-232, RS-485 and Combus
Communication Speed
Up to 115.200 baud (automatic detection)
Firmware Flash
Memory
256K
RAM Memory
512K; protected by a lithium battery
Network Autonomy
Distributed data and processing
Certifications / Listing
CE, FCC, UL294 listed