3-3.Air Velocity Analog Output Setting
The output can be selected from the current output (4 to 20 mA) and the voltage
output (0 to 5 V). To change output, use the DIP switch of air velocity
The range of air velocity is also selectable.
The factory setting is: DIP Switch setting 4; air velocity (0 to 50.0 m/s); and current output.
To change the air velocity range, use the rotary switch. Select the air velocity range from 5
ranges as the table shows below.
The factory setting is No. 4 (air velocity range: 0 to 50.00 m/s, current output: 4 to 20 mA).
No.
Air velocity
range
[m/s]
Current output
range
[mA]
Voltage output
range
[V]
0
0 to 2.00
4 to 20
0 to 5
1
0 to 5.00
4 to 20
0 to 5
2
0 to 10.00
4 to 20
0 to 5
3
0 to 25.00
4 to 20
0 to 5
4 to 9
0 to 50.00
4 to 20
0 to 5
Example: For the probe 0975-31, air velocity 10.0 m/s, DIP Switch 3 (Range: 25.0 m/s)
While changing the output setting, be sure to shut off power supply.