Item Field
Access
Level
Description
Range
Section
LT
D
USER
INS
T
AD
V
C1
C1
The differential that the control is to use when it is
operating the boiler.
Boil SENS = SUP
The location of the boiler sensor. This affects
operation of the boiler contact.
LITE, MED,
HEVY
Default = MED
The thermal mass characteristics of the boiler
that is being used.
Boil SENS = SUP
SUP (Supply)
RET (Return)
NONE
Default = SUP
The time that the actuating motor requires to
operate from fully closed to fully open.
30 to 230 sec
Default = 150 sec
Adjust
Menu (2 of 2)
AUTO, 2 to 42°F
(AUTO, 1 to 23°C)
Default = AUTO
C2
C1
C3
C1
The maximum temperature allowed for the boiler
target temperature.
Boil SENS = SUP
120 to 225°F, OFF
(49 to 107°C, OFF)
Default = 210°F
(99°C)
The minimum temperature allowed for the boiler
target temperature.
Boil SENS
≠
NONE
OFF, 80 to 180°F
(OFF, 27 to 82°C)
Default = 140°F
(60°C)
C1
The time delay the control can expect between the
time the boiler contact closes and the burner fires.
Boil SENS = SUP
C1
0:00 to 3:00 min
(1 sec. increments)
Default = 0:10 min
Occ
35 to 100°F, OFF
(2 to 38°C, OFF)
Default = 70°F
(21°C)
The system’s warm weather shut down during the
Occupied period.
B1
UnOcc
The system’s warm weather shut down during the
UnOccupied period.
Dip switch = Setback
B1
35 to 100°F, OFF
(2 to 38°C, OFF)
Default = 60°F
(16°C)
B1
The maximum length of time that the boiler pump
will continue to operate after the mixing demand
has been removed.
OFF,
0:10 to 40:00 min
Default = 0:20
min
Enables or disables the Soft Start feature in the
control.
NONE, MIX
Default = NONE
B1
A
The frequency with which the control will
exercise the pumps and v alv es that are
operated by the control.
30 to 240 hr,
OFF
Default = 70 hr
Actual
Setting
Note:
= The Item is set to,
≠
The Item is not set to