21 of 32
© 2003 D 362e - 06/03
-67 to 149°F
(-55 to 65°C)
Item Field
Access
Level
Description
Range
Section
LT
D
USER
INS
T
AD
V
R
TU 062e
R
TU 063e
Current outdoor air temperature.
RTU
View
Menu (2 of 2)
B2
Current floor (slab) sensor temperature.
REMOTE 3 = FLOR
-58 to 167°F
(-50 to 75°C)
35 to 100°F
(2 to 38°C)
Default = 70°F
(21°C)
B1
Item Field
Access
Level
Description
Range
Section
LT
D
USER
INS
T
AD
V
R
TU 062e
R
TU 063e
The desired room air temperature during
an Occupied period for the heating zone.
Note:
There is only a ±3°F (±1°C)
adjustment in the LTD access level
Actual
Setting
Occ
RTU
Adjust
Menu (1 of 1)
UnOcc
B1
The desired room air temperature during an
UnOccupied period for the heating zone.
Note:
There is only a ±3°F (±1°C)
adjustment in the LTD access level
DIP switch = Setback
35 to 100°F
(2 to 38°C)
Default = 65°F
(18°C)
B1
The amount of morning boost.
DIP switch = Setback
OFF, 0:20 to 8:00 hr
Default = OFF
Selects whether the RTU is to use its
internal air sensor.
OFF, AIR
Default = AIR
This item allows for remotely adding a 10K
sensor to the RTU. Applications are for
temperature averaging.
NONE, AIR
Default = NONE
This item allows for remotely adding
a second 10K sensor to the RTU.
Applications
are
for
temperature
averaging.
NONE, AIR
Default = NONE
This item allows for remotely adding a
third 10K air sensor to the RTU, or a 10K
slab sensor to measure slab temperature.
MIX MIN = OFF
(for Slab Sensor only)
NONE, AIR,
FLOR
Default = NONE
The minimum target temperature at the
floor (slab) sensor when not in WWSD.
REMOTE 3 = FLOR
OFF, 35 to 120°F
(OFF, 2 to 49°C)
Default = 70°F
(21°C)
The maximum target temperature at the
flor (slab) sensor.
REMOTE 3 = FLOR
40 to 150°F
(4 to 66°C)
Default = 90°F
(32°C)
Note:
= The Item is set to,
≠
The Item is not set to
Note:
= The Item is set to,
≠
The Item is not set to