© 2003 D 362e - 06/03
18 of 32
Adjust
Menu (1 of 2)
B1
UnOcc
B2
B2
B1
B1
B1
B1
B1
B1
The desired room air temperature during an
UnOccupied period.
Dip switch = Setback
No RTU connected
The device that is to be connected to the 10K
input terminal.
No RTU connected
The minimum temperature at the floor (slab)
sensor as long as the control is not in WWSD.
10K = FLOR
MIX MIN = OFF
No RTU connected
The maximum temperature at the floor (slab)
sensor.
10K = FLOR
MIX MIN = OFF
No RTU connected
The design indoor air temperature used in the
heat loss calculations for the heating system.
The design supply water temperature used in the
heat loss calculations for the heating system.
The design outdoor air temperature used in the
heat loss calculations for the heating system.
The minimum supply water temperature for the
mixing system.
NONE, INDR,
ZoIn, FLOR, (only)
if MIX MIN = OFF
Default = NONE
OFF, 35 to 120°F
(OFF, 2 to 49°C)
Default = 70°F
(21°C)
40 to 150°F
(4 to 66°C)
Default = 90°F
(32°C)
OFF, 0:20 to 8:00 Hr
Default = OFF
U/F1 (Screeded),
U/F2 (Plated), UNIT,
FIN, RAD(iator),
BASE(board)
Default = U/F1
70 to 220°F
(21 to 104°C)
Default = 120°F
(49°C)
The amount of morning boost.
Dip switch = Setback
No RTU connected
10K
≠
ZoIn
The type of terminal units that are being used in
the heating system.
35 to 100°F
(2 to 38°C)
Default = 70°F
(21°C)
B2
Occ
The desired room air temperature during an
Occupied period.
Note:
There is only a ±3°F (±1°C) adjustment in
the LTD access level.
No RTU connected
-60 to 32°F
(-51 to 0°C)
Default = 10°F
(-12°C)
B1
35 to 100°F
(2 to 38°C)
Default = 70°F
(21°C)
35 to 100°F
(2 to 38°C)
Default = 65°F
(18°C)
OFF, 35 to 150°F
(OFF, 2 to 66°C)
Default = OFF)
The maximum supply water temperature for the
mixing system.
B1
80 to 212°F
(27 to 99°C)
Default = 140°F
(60°C)
Item Field
Access
Level
Description
Range
Section
LT
D
USER
INS
T
AD
V
Actual
Setting
Note:
= The Item is set to,
≠
The Item is not set to