background image

 

G-SA060-002

 

 

4.Connecting cables 

Use 14 AWG minimum, insulated for 90

 minimum cables. 

Stranded Copper only. 

When connecting cables, push the plus and minus connectors against each 

other while twisting them until they are fully engaged. 
 
 
 
 
 
 
 

Plus cable connector: PV-KST3II UR (Multi-Contact USA) 
Minus cable connector: PV-KBT3II UR (Multi-Contact USA) 

 
 

Each PV has MC Connector system for photovoltaic, which is supplied from 

Multi-Contact USA. You should use the same UL recognized connector as written 
above.  

The MODULES employ factory assembled Multi-Contact connectors for 

interconnection between the MODULES during array assembly in the field. As 
these connectors can only be assembled in the factory, we recommend the use of 
commercially available output wiring products, such as (USE-MCUL-50 made by 
O&S California, Inc.) so that the final array output wiring can be made to a 
permanent wiring system in accordance with Article 690-31 of the National 
Electrical Code. 

More than five (5) MODULES should not be connected in series. And each 

string should have a blocking diode or a fuse, which is a 3A of capacity.   

See the Attachment A: Instruction for using G-type (UL grade). 
 

5.Ground-connecting 

All the MODULES should be ground-connected with the ground holes 
(marked ‘GR’) of the MODULES.     

http://www.wholesalesolar.com/solar-panels.html

Summary of Contents for G-SA060

Page 1: ...060 002 KANEKA Thin Film PV Installation Manual MODULE TYPE G SA060 KANEKA CORPORATION 3 2 4 NAKANOSHIMA KITA KU OSAKA 530 8288 JAPAN reference No G SA060 002 http www wholesalesolar com solar panels...

Page 2: ...Follow the procedure in this manual when installing the MODULE and its platform Beware of electric shock and short circuit as the MODULE generates high tension current when exposed to light Wear a saf...

Page 3: ...G SA060 002 1 Dimensions http www wholesalesolar com solar panels html...

Page 4: ...Pmax Vpm V 67 0 Current at Pmax Ipm A 0 90 Tolerance 10 Max System Voltage V 530 Fire Rating Class C Dimension mm 990 2 5 x 960 2 5 Depth mm 40 1 0 Weight kg 13 7 REMARK 1 During initial 6 weeks of op...

Page 5: ...on UL Listed MODULES should be multiplied by a factor of 125 when determining component voltage ratings conductor capacities fuse sizes and size of controls connected to the MODULE output Refer to Art...

Page 6: ...Installation shall be in accordance with CSA 22 1 Safety Standard for Electrical Installations Canadian Electrical Code Part 1 All mounting hardware shall be stainless steel Method 1 Fix the MODULES t...

Page 7: ...the 2 cramps must be 660 950mm Optimize the tightness of the cramps with greatest care so that the MODULES will not come off and so that the cramps will not break the frames of the MODULES and or glas...

Page 8: ...s for interconnection between the MODULES during array assembly in the field As these connectors can only be assembled in the factory we recommend the use of commercially available output wiring produ...

Page 9: ...ew needs to provide sufficient torque to ensure that the lug is mechanically secure 4 Connect a minimum 10AWG solid conductor copper ground wire to the ground lug You will use stainless steel hardware...

Page 10: ...G SA060 002 7 Limitation See the Attachment A Instruction for using G type UL grade http www wholesalesolar com solar panels html...