G-SA060-002
4.Connecting cables
Use 14 AWG minimum, insulated for 90
℃
minimum cables.
Stranded Copper only.
When connecting cables, push the plus and minus connectors against each
other while twisting them until they are fully engaged.
Plus cable connector: PV-KST3II UR (Multi-Contact USA)
Minus cable connector: PV-KBT3II UR (Multi-Contact USA)
Each PV has MC Connector system for photovoltaic, which is supplied from
Multi-Contact USA. You should use the same UL recognized connector as written
above.
The MODULES employ factory assembled Multi-Contact connectors for
interconnection between the MODULES during array assembly in the field. As
these connectors can only be assembled in the factory, we recommend the use of
commercially available output wiring products, such as (USE-MCUL-50 made by
O&S California, Inc.) so that the final array output wiring can be made to a
permanent wiring system in accordance with Article 690-31 of the National
Electrical Code.
More than five (5) MODULES should not be connected in series. And each
string should have a blocking diode or a fuse, which is a 3A of capacity.
See the Attachment A: Instruction for using G-type (UL grade).
5.Ground-connecting
All the MODULES should be ground-connected with the ground holes
(marked ‘GR’) of the MODULES.
http://www.wholesalesolar.com/solar-panels.html