3.Installation of the MODULES 

 
The assembly is to be mounted over a fire resistant roof covering rated for the 

application. 

5 in/ft (127mm/305mm) required to maintain UL fire class rating. 
Artificially concentrated sunlight shall not be directed on the MODULE. 
See the Attachment A: Instruction for using G-type (UL grade). 

 

(Remark for C-UL)   
Installation shall be in accordance with CSA 22.1, Safety Standard for Electrical 
Installations, Canadian Electrical Code, Part 1. 
 
All mounting hardware shall be stainless steel 

Method (1) 

Fix the MODULES to rails with M6 bolts and nuts (4 pairs per module). The 

platform of the MODULES should have sufficient strength. 

[the MODULE mounting diagram] 

M6 Bolt

Flat Washer

Spring Washer

M6 Nut

M6 Bolt

Flat Washer

Spring Washer

M6 Nut

 

 
 

Method (2) 

Fix the MODULES to rails with clamps as shown in the picture below. 
 
 
 
 
 

http://www.wholesalesolar.com/solar-panels.html

Summary of Contents for G-SA060

Page 1: ...060 002 KANEKA Thin Film PV Installation Manual MODULE TYPE G SA060 KANEKA CORPORATION 3 2 4 NAKANOSHIMA KITA KU OSAKA 530 8288 JAPAN reference No G SA060 002 http www wholesalesolar com solar panels...

Page 2: ...Follow the procedure in this manual when installing the MODULE and its platform Beware of electric shock and short circuit as the MODULE generates high tension current when exposed to light Wear a saf...

Page 3: ...G SA060 002 1 Dimensions http www wholesalesolar com solar panels html...

Page 4: ...Pmax Vpm V 67 0 Current at Pmax Ipm A 0 90 Tolerance 10 Max System Voltage V 530 Fire Rating Class C Dimension mm 990 2 5 x 960 2 5 Depth mm 40 1 0 Weight kg 13 7 REMARK 1 During initial 6 weeks of op...

Page 5: ...on UL Listed MODULES should be multiplied by a factor of 125 when determining component voltage ratings conductor capacities fuse sizes and size of controls connected to the MODULE output Refer to Art...

Page 6: ...Installation shall be in accordance with CSA 22 1 Safety Standard for Electrical Installations Canadian Electrical Code Part 1 All mounting hardware shall be stainless steel Method 1 Fix the MODULES t...

Page 7: ...the 2 cramps must be 660 950mm Optimize the tightness of the cramps with greatest care so that the MODULES will not come off and so that the cramps will not break the frames of the MODULES and or glas...

Page 8: ...s for interconnection between the MODULES during array assembly in the field As these connectors can only be assembled in the factory we recommend the use of commercially available output wiring produ...

Page 9: ...ew needs to provide sufficient torque to ensure that the lug is mechanically secure 4 Connect a minimum 10AWG solid conductor copper ground wire to the ground lug You will use stainless steel hardware...

Page 10: ...G SA060 002 7 Limitation See the Attachment A Instruction for using G type UL grade http www wholesalesolar com solar panels html...