BBREVIATIONS

 

NMS    NANO/MAR System   
NCP 

NANO Control Panel   

NETB  NANO ETB/MAR/BOX (extinguishers terminal box)   
PDS 

Programming Dip Switch 

 

CP 

Connection Point 

 

PSU 

Power Supply   

VFC 

Volt free contact 

 

EOL 

End of line device 

 

PCB 

Printed circuit board 

3

 

I

MPORTANT 

N

OTES 

 

PLEASE

 

READ

 

CAREFULLY 

This quick guide manual is an addition to the existing DIOM of the NANO MAR SYSTEM dated January 
1,  2023  version  1.2  from  the  K&G  Groep  BV.  This  quick  guide  should  be  read  thoroughly  and 
understood before installing of the NMS is undertaken. It is assumed that the person installs, testing 
and commissioning the system, is familiar with the terminology and the objective of the equipment. 
The NCP and the corresponding connections must be properly connected to the NETB and KG/KVB 
Stat-X extinguishing  aerosol  generators by an appropriately qualified and  competent person.  The 
equipment  is  only  guaranteed  in  accordance  with  the  DIOM  of  the  NANO  MAR  SYSTEM  dated 
January 1, 2023 version 1.2.   

4

 

C

ERTIFICATION

 

 

The NMS has successfully passed CE and FCC, EMC testing according to  EN 50130, EN 61000, EN 
55016,  47  CFR15-ICES-003,  ANSI 63.4,  IEC60945-pt11  and a  DNV  marine  type  approval  according 
the  DNV  Class  Guideline  0339-2021,  certificate  TAA000037H.  For  that  the  NMS  has  endured 
extensive environmental tests such as vibration, dry heat, damp heat and cold tests in accordance 
with the requirements of the DNV-CG 0339 standard. 

5

 

P

REFASE

 

In our standard DIOM is all written for installing/commissioning and servicing the NMS, NCP control 
panel and extinghuishers terminal box NETB. This quick guide is a shortened step-by-step plan who 
guides  you  to  put  the  system  into  operation.  The  NMS  is  a  multi-functional  controller  for  fire 
detection and fire extinguishing release systems. This quick guide only covers the NMS intended for 
rooms  on  vessels.  For  other  applications,  please  refer  to  the  standard  and  comprehensive 
installation instructions. 

 

6

 

P

URPOSE

 

The purpose of this document is to describe installation, service and troubleshooting of the NMS. 
Please  note  that  only  aspects  regarding  the  NMS  itself  are  covered  by  this  manual.  Physical 
placement of aerosol generators and cables etc. is not handled as these issues are typically to be 
specified  specifically  for  each  installation.  The  purpose  of  the  NMS  is  to  control  and  monitor  a 
number of aerosol generators mounted on a ship as part of a fire extinguishing system.

 

Summary of Contents for NANO MARINE

Page 1: ...this manual may be reproduced stored in an automated database or made public in any form or by any means either electronically mechanically or by photocopying recording or in any other way without pri...

Page 2: ...EXTINGUISHERS TO NETB 7 12 CONNECTING CABLE TO EXTINGHUISHERS CONNECTOR 8 13 SOUNDER OUTPUT 9 14 EXTERNAL EXTINGHUISING RELEASE 9 15 ROADMAP FOR FINAL COMMISSIONING 10 15 1 POWER OFF STEP ONE 10 15 2...

Page 3: ...CFR15 ICES 003 ANSI 63 4 IEC60945 pt11 and a DNV marine type approval according the DNV Class Guideline 0339 2021 certificate TAA000037H For that the NMS has endured extensive environmental tests such...

Page 4: ...e two extinguisher terminal boxes NETB These NETB boxes must be placed outside but in the immediate vicinity of the protected room One is suitable for connecting up to 5 extinguishers and one for up t...

Page 5: ...2 CP 18 CP 17 see wiring diagram 10K 10K 10K RELEASE HOLD 10K not in use Sounder Hold PSU 2 8V DC to 28V DC 8 7 6 5 4 3 2 1 ON OFF DIP NC NO C NC NO C NC NO C 8 7 6 5 4 3 2 1 extinguishant delay timer...

Page 6: ...IP NC NO C NC NO C NC NO C 8 7 6 5 4 3 2 1 extinguishant delay timer switches relay 1st or 2nd stage fire single or dual zone alarm vehicle mode extinguishing release output current puls or voltage EO...

Page 7: ...vehicle mode extinguishing release output current puls or voltage EOL 10K RESITOR EOL 10K RESITOR EOL 10K RESITOR EOL 10K RESITOR external release external release external hold release external hold...

Page 8: ...Strip cable jacket at the end of the cable meant to connected the fire extinguisher and finish the two wires with insulated crimp bootlace ferrules 3 Follow stricktly the wring specifications of the c...

Page 9: ...i 2 3 4 i 5 i 6 i 7 8 i 9 OPTION OPTION OPTION OPTION PSU 1 PSU 2 NANO EXTINGUISHING RELEASING PANEL NCP ON THE BRIGDE FROM NCP TO NETB WITH THREE 2 CORE CABLES 1 1 NANO 22 1 2 NANO 23 2 1 NANO 24 2 2...

Page 10: ...all connected correctly 4 Check the last ETB for the end off line diode switch DISCONNECT EXTINGHUISHER Move the disconnect switch in the YES position and the aerosol extinguisher is disabled and can...

Page 11: ...3 on off ETB 4 on off EXT 1 EXT 2 ETB 1 on off ETB 2 on off IN The ETB dip switch positions on a NETB 10 in use with 7 Stat X extinguishers End Of Line switch Disconnect Extinguisher switch 15 3 EXAM...

Page 12: ...AL RELEASE ONLY 1 Front NCP manual release ONLY fire detectors are not in use PDS 1 OFF 2 The vehicle mode is disabled is not in use PDS 2 OFF 3 Activation of electrical igniters for aerosol fire exti...

Page 13: ...the connection diagram below The recommended setting gives the best and deviating alarm signal compared to the usual evacuation alarm signal on vessels Recommended setting sounder beacon C D OFF TONE...

Page 14: ...servability of the of the optical alarm signal in the protected area In a noisy environment the optical alarm signal is the main warning element Recommended setting sounder beacon C D OFF IN IN TONES...

Page 15: ...eous the extinguishing release buttons on the front of the NCP 9 Confirmation of extinguisher activation As confirmation of a successful extinguishment activation the red LEDs on the extinguishers ter...

Page 16: ...y form or by any means either electronically mechanically or by photocopying recording or in any other way without prior written permission from K G GROEP B V The policy of the K G GROEP B V is one of...

Reviews: