ESTING THE INSTALLATION

 

1   Open the NETB. 

Disconnect the extinghuishers on the NETB. 

After disconnecting the extinghuishers you get an fault       

        warning on the NCP.   

 

 

 

 

 

 

 

Activate the extinguishing by pressing simultaneous both yellow 

          extinguishing release buttons on the NETB door. 

Confirmation of extinguisher activation.   

            

      The alarm should sound, ventilation should stop (if     

                           connected) after the activation delay (installed delay 
                           time) the released light on the front panel should as  
                          confirmation of a successful activation, the red LEDs on the extinguishers terminal       
                          board will flash and the red extinguishing released LED on the NCP.  
                          lite up. 

Reset the system by pressing the reset button on the NCP. 

Repeats activate the extinguishing release by pressing simultaneous the  

 

extinguishing release buttons on the front of the NCP. 

 

 

Confirmation of extinguisher activation   

                          As confirmation of a successful extinguishment activation, the red LEDs on the         
                          extinguishers terminal board will flash, and the red extinguishing released LED             
                          on the NCP lite up. 

 

 

 

10  Reset the system by pressing the reset button on the NCP. 

Make sure everyone leaves the engine room for safety reasons and that no 
activation switches are active. 

11  Restore the system and re-connected the extinguishers. 

  

  

 

 

 

 

12  The fault LED on the NCP goes out. Only the green Power LED and the Manual Only LED light 

up to indicate that the system is ready for use. 

Disconnect extinguisher 

 

 

 

 

Move the disconnect switch of all in the YES position. 

  

The aerosol extinguisher is disabled and can not be activated.    
A disablement will be signalized as fault on the NCP. 

Connect extinguishers  

Move the disconnect switch in the NO position and the aerosol extinguisher 
is connected to the system and can be activated.  

 

Summary of Contents for NANO MARINE

Page 1: ...this manual may be reproduced stored in an automated database or made public in any form or by any means either electronically mechanically or by photocopying recording or in any other way without pri...

Page 2: ...EXTINGUISHERS TO NETB 7 12 CONNECTING CABLE TO EXTINGHUISHERS CONNECTOR 8 13 SOUNDER OUTPUT 9 14 EXTERNAL EXTINGHUISING RELEASE 9 15 ROADMAP FOR FINAL COMMISSIONING 10 15 1 POWER OFF STEP ONE 10 15 2...

Page 3: ...CFR15 ICES 003 ANSI 63 4 IEC60945 pt11 and a DNV marine type approval according the DNV Class Guideline 0339 2021 certificate TAA000037H For that the NMS has endured extensive environmental tests such...

Page 4: ...e two extinguisher terminal boxes NETB These NETB boxes must be placed outside but in the immediate vicinity of the protected room One is suitable for connecting up to 5 extinguishers and one for up t...

Page 5: ...2 CP 18 CP 17 see wiring diagram 10K 10K 10K RELEASE HOLD 10K not in use Sounder Hold PSU 2 8V DC to 28V DC 8 7 6 5 4 3 2 1 ON OFF DIP NC NO C NC NO C NC NO C 8 7 6 5 4 3 2 1 extinguishant delay timer...

Page 6: ...IP NC NO C NC NO C NC NO C 8 7 6 5 4 3 2 1 extinguishant delay timer switches relay 1st or 2nd stage fire single or dual zone alarm vehicle mode extinguishing release output current puls or voltage EO...

Page 7: ...vehicle mode extinguishing release output current puls or voltage EOL 10K RESITOR EOL 10K RESITOR EOL 10K RESITOR EOL 10K RESITOR external release external release external hold release external hold...

Page 8: ...Strip cable jacket at the end of the cable meant to connected the fire extinguisher and finish the two wires with insulated crimp bootlace ferrules 3 Follow stricktly the wring specifications of the c...

Page 9: ...i 2 3 4 i 5 i 6 i 7 8 i 9 OPTION OPTION OPTION OPTION PSU 1 PSU 2 NANO EXTINGUISHING RELEASING PANEL NCP ON THE BRIGDE FROM NCP TO NETB WITH THREE 2 CORE CABLES 1 1 NANO 22 1 2 NANO 23 2 1 NANO 24 2 2...

Page 10: ...all connected correctly 4 Check the last ETB for the end off line diode switch DISCONNECT EXTINGHUISHER Move the disconnect switch in the YES position and the aerosol extinguisher is disabled and can...

Page 11: ...3 on off ETB 4 on off EXT 1 EXT 2 ETB 1 on off ETB 2 on off IN The ETB dip switch positions on a NETB 10 in use with 7 Stat X extinguishers End Of Line switch Disconnect Extinguisher switch 15 3 EXAM...

Page 12: ...AL RELEASE ONLY 1 Front NCP manual release ONLY fire detectors are not in use PDS 1 OFF 2 The vehicle mode is disabled is not in use PDS 2 OFF 3 Activation of electrical igniters for aerosol fire exti...

Page 13: ...the connection diagram below The recommended setting gives the best and deviating alarm signal compared to the usual evacuation alarm signal on vessels Recommended setting sounder beacon C D OFF TONE...

Page 14: ...servability of the of the optical alarm signal in the protected area In a noisy environment the optical alarm signal is the main warning element Recommended setting sounder beacon C D OFF IN IN TONES...

Page 15: ...eous the extinguishing release buttons on the front of the NCP 9 Confirmation of extinguisher activation As confirmation of a successful extinguishment activation the red LEDs on the extinguishers ter...

Page 16: ...y form or by any means either electronically mechanically or by photocopying recording or in any other way without prior written permission from K G GROEP B V The policy of the K G GROEP B V is one of...

Reviews: