20
Kamstrup A/S • 55122070_A2_GB_07.2017
MULTICAL® 603
8.12 LON FT-X3 + 2 pulse inputs, type HC-003-60
The LON FT-X3 module is designed for use in
free topology communication TP/FT-10. The
module is compatible with LONWORKS® 2.0
and supports high-speed communication up to
78600 baud.
The LON module enables the integration of the
energy meters in building automation systems
or in industrial applications. The LON module
is delivered with bar codes with imprinted LON
Node ID to ease the commissioning.
The module is power-supplied by the 24 VAC or
230 VAC power supply in MULTICAL®. The power
supply must be in the high-power version. It is
not possible to battery-supply MULTICAL®.
8.13 BACnet MS/TP + 2 pulse inputs, type HC-003-66
The BACnet module is designed for use in
free topology communication. The module is
compatible with ASHRAE 135 and supports
high-speed communication up to 76800 baud.
The BACnet module enables the integration
of the energy meters in building automation
systems or in industrial applications.
The BACnet module is BACnet-certified and
registered in the BTL list.
The module is power-supplied by the 24 VAC or
230 VAC power supply in MULTICAL®. MULTICAL®
cannot be battery-supplied.
8.14 pulse inputs, type HC-003-67
Modbus RTU slave module. Communication
on RS485 with twisted shielded cables via the
terminals 137, 138 an 139.
The meter must be supplied by 24 VAC or 230
VAC.