MULTICAL® 403

6.2  Mains supply

MULTICAL® 403 is available with supply 
modules for either 24 VAC or 230 VAC.
The modules are protection class II and are 
connected via two-wire cable (without earth) 
through the big cable bush, the second one 
from the right, at the bottom of the connection 
base. Use connecting cable with an outer 
diameter of 5-10 mm and ensure correct cable 
stripping as well as correct mounting of cable 
relief.
If connecting to 230 VAC, it is important to 
make sure that the whole installation complies 
with current regulations. The supply cable 
must not be protected by a fuse larger than 
the one permitted for the given cable size, see 
examples below.

Supply cable

Max. Fuse

2 x 0.75 mm

2

  

(accessory from Kamstrup A/S)

6 A

2 x 1.0 mm

2

10 A

In connection with other types of installations 
or requirements for larger fuses than the 
ones listed above, it is necessary to consult a 
certified electrician for an individual evaluation 
of how the type of installation in question 
should be carried out.
In addition please note that work on the fixed 
installations, including any intervention in the 
fuse box, must be carried out by an authorized 
electrician. 

Black

Red

61
60

97

98

24 VAC supply

24 VAC

3.

V

24 VAC

E.g. transformer 230/24 V, type 66-99-403, 
can be used.

Note: 

MULTICAL® 403 cannot be powered 
by 24 VDC.

Black

Red

61
60

27

28

230 VAC supply

230 VAC

3.

V

230 VAC

This module is used when the meter is supplied 
directly by the mains. 

Note: 

External supply must only be connected 
to the supply module.

Summary of Contents for MULTICAL 403

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions MULTICAL 403...

Page 2: ...o uk Registered Address ABLE Instruments Controls Ltd Cutbush Park Danehill Lower Earley Reading Berkshire RG6 4UT UK Web able co uk E commerce 247able com Installation and user s guide MULTICAL 403 K...

Page 3: ...130 C MID designation Mechanical environment Class M1 and M2 Electromagnetic environment Class E1 housing light industry The meter s control cables must be drawn at min 25 cm distance from other insta...

Page 4: ...ect sensor in MULTICAL 403 flow sensor 8 3 2 Flow sensor position 9 3 3 Mounting of MULTICAL 403 flow sensor 10 3 4 Installation examples 11 3 5 Humidity and condensation 11 4 Mounting the calculator...

Page 5: ...meter In case of incorrect mounting Kamstrup s guarantee obligations no longer apply Please note that the following installation conditions must be obeyed Pressure stage PN16 PN25 see marking The mete...

Page 6: ...urn pipe For mounting in the calculator see the paragraph Electrical connection Note The sensor cables must neither be exposed to jerking nor pulling Please be aware of this when binding the cables an...

Page 7: ...kets can be mounted in e g a welding sleeve or in a 45 lateral Y piece The tip of the sensor pocket must at least reach the center of the flow pipe Push the temperature sensors as deep as possible int...

Page 8: ...5121739_A3_GB_04 2016 MULTICAL 403 2 3 Temperature sensor compatibility with flow sensors The size of the flow sensor determines which temperature sensors you can use and how they are mounted The belo...

Page 9: ...ensor 3 1 Mounting of couplings and short direct sensor in MULTICAL 403 flow sensor The short direct sensor from Kamstrup may be installed in PN16 installations only The blind plug which is mounted in...

Page 10: ...le position in closed systems E A flow sensor ought not to be placed immediately after a valve with the exception of block valves ball valve type which must be fully open when not used for blocking F...

Page 11: ...Cutbush Park Danehill Lower Earley Reading Berkshire RG6 4UT UK Web able co uk E commerce 247able com 10 Kamstrup A S 55121739_A3_GB_04 2016 MULTICAL 403 3 3 Mounting of MULTICAL 403 flow sensor 90 9...

Page 12: ...eading Berkshire RG6 4UT UK Web able co uk E commerce 247able com 11 Kamstrup A S 55121739_A3_GB_04 2016 MULTICAL 403 3 4 Installation examples Threaded meter Flow from the left Flow from the right Fl...

Page 13: ...wall mounted Furthermore MULTICAL 403 in cooling applications must be the condensation proof version type 403 T The construction of MULTICAL 403 always provides minimum installation depth in connectio...

Page 14: ...s Controls Ltd Cutbush Park Danehill Lower Earley Reading Berkshire RG6 4UT UK Web able co uk E commerce 247able com 13 Kamstrup A S 55121739_A3_GB_04 2016 MULTICAL 403 4 3 Position of calculator If t...

Page 15: ...splayed in in TECH loop reading 2 017 00 for indication of current errors in MULTICAL 403 The info code consists of 8 digits and each functionality has its own digit dedicated to the indication of rel...

Page 16: ...ne D cell battery Optimal battery lifetime is obtained by keeping the battery temperature below 30 C e g by wall mounting The voltage of a lithium battery is almost constant throughout the lifetime of...

Page 17: ...on complies with current regulations The supply cable must not be protected by a fuse larger than the one permitted for the given cable size see examples below Supply cable Max Fuse 2 x 0 75 mm2 acces...

Page 18: ...nd valves to establish water flow through the system Activate the left front key primary key of MULTICAL 403 to change display reading and check that the displayed values for temperatures and water fl...

Page 19: ...for connection of extra meters with either Reed switch output or passive electronic pulse output Minimum pulse duration is 30 ms max pulse frequency is 3 Hz If a module with pulse inputs is mounted in...

Page 20: ...06 D SUB 9F or 66 99 098 USB type A with the following connections 62 Brown DAT 63 White REQ 64 Green GND 9 5 Data pulse outputs type HC 003 11 The data terminals are used for connection of e g a PC T...

Page 21: ...functionality The module is powered by the connected master 9 8 Wireless M Bus pulse inputs type HC 003 30 The wireless M Bus module has been designed to form part of Kamstrup s hand held Wireless M B...

Page 22: ...lude secondary readings and therefore the index number always consists of 4 digits In SETUP loop the right key secondary key is used for accessing individual readings with the purpose of changing para...

Page 23: ...e values Four minutes after the latest activation of any front key reading automatically changes to consumed energy Display readings Consumed energy in kWh MWh or GJ Activate to view yearly and monthl...

Reviews: