MULTICAL® 403
6.2 Mains supply
MULTICAL® 403 is available with supply
modules for either 24 VAC or 230 VAC.
The modules are protection class II and are
connected via two-wire cable (without earth)
through the big cable bush, the second one
from the right, at the bottom of the connection
base. Use connecting cable with an outer
diameter of 5-10 mm and ensure correct cable
stripping as well as correct mounting of cable
relief.
If connecting to 230 VAC, it is important to
make sure that the whole installation complies
with current regulations. The supply cable
must not be protected by a fuse larger than
the one permitted for the given cable size, see
examples below.
Supply cable
Max. Fuse
2 x 0.75 mm
2
(accessory from Kamstrup A/S)
6 A
2 x 1.0 mm
2
10 A
In connection with other types of installations
or requirements for larger fuses than the
ones listed above, it is necessary to consult a
certified electrician for an individual evaluation
of how the type of installation in question
should be carried out.
In addition please note that work on the fixed
installations, including any intervention in the
fuse box, must be carried out by an authorized
electrician.
Black
Red
61
60
97
98
24 VAC supply
24 VAC
3.
6
V
24 VAC
E.g. transformer 230/24 V, type 66-99-403,
can be used.
Note:
MULTICAL® 403 cannot be powered
by 24 VDC.
Black
Red
61
60
27
28
230 VAC supply
230 VAC
3.
6
V
230 VAC
This module is used when the meter is supplied
directly by the mains.
Note:
External supply must only be connected
to the supply module.