Display readings are based on 

DDD-code 210

. At kamstrup.com you find a selection of interactive user guides based 

on other DDD-codes.

User Guide

Energy measurement

MULTICAL® 403 functions as follows:

The flow sensor

 registers the quantity of water which circulates through the system in cubic metres (m

3

).

The temperature sensors 

mounted in inlet and outlet pipes register the cooling, i.e. the difference between inlet and 

outlet temperatures.

MULTICAL® 403

 calculates energy consumption on the basis of volume of water and temperature difference.

Readings in the display

When the primary key   is activated, a new primary reading is displayed. The secondary key 

 is used to display 

historical readings and average values.
Four minutes after the latest activation of any front key, reading automatically changes to consumed energy.

Display readings

Consumed energy in kWh, 

MWh or GJ.

Activate 

 to view yearly 

and monthly log values. 

Volume of water consumed.

Activate 

 to view yearly 

and monthly log values. 

Number of operating hours.

Activate 

 to view error hour counter 

(number of operating hours with an 

error).

Current inlet temperature.

Activate 

 to view yearly and 

monthly average values.

Current outlet temperature.

Activate 

 to view yearly and 

monthly average values.

Current differential 

temperature (cooling).

Current water flow.

Activate 

 to view the max value 

of the current year followed by the 

max value of the current month.

Current heating effect.

Activate 

 to view the max value 

of the current year followed by the 

max value of the current month.

Accumulated consumption on 

inputs A and B. 

In this example for a connected 

water meter.

Current information code.

(Contact your utility company 

if the value differs from 

”00000000”).

The first digits of the customer 

number. 

Activate 

 to view the last digits 

of the customer number.

Depending on display code 

additional readings are 

displayed here.

Summary of Contents for MULTICAL 403

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions MULTICAL 403...

Page 2: ...o uk Registered Address ABLE Instruments Controls Ltd Cutbush Park Danehill Lower Earley Reading Berkshire RG6 4UT UK Web able co uk E commerce 247able com Installation and user s guide MULTICAL 403 K...

Page 3: ...130 C MID designation Mechanical environment Class M1 and M2 Electromagnetic environment Class E1 housing light industry The meter s control cables must be drawn at min 25 cm distance from other insta...

Page 4: ...ect sensor in MULTICAL 403 flow sensor 8 3 2 Flow sensor position 9 3 3 Mounting of MULTICAL 403 flow sensor 10 3 4 Installation examples 11 3 5 Humidity and condensation 11 4 Mounting the calculator...

Page 5: ...meter In case of incorrect mounting Kamstrup s guarantee obligations no longer apply Please note that the following installation conditions must be obeyed Pressure stage PN16 PN25 see marking The mete...

Page 6: ...urn pipe For mounting in the calculator see the paragraph Electrical connection Note The sensor cables must neither be exposed to jerking nor pulling Please be aware of this when binding the cables an...

Page 7: ...kets can be mounted in e g a welding sleeve or in a 45 lateral Y piece The tip of the sensor pocket must at least reach the center of the flow pipe Push the temperature sensors as deep as possible int...

Page 8: ...5121739_A3_GB_04 2016 MULTICAL 403 2 3 Temperature sensor compatibility with flow sensors The size of the flow sensor determines which temperature sensors you can use and how they are mounted The belo...

Page 9: ...ensor 3 1 Mounting of couplings and short direct sensor in MULTICAL 403 flow sensor The short direct sensor from Kamstrup may be installed in PN16 installations only The blind plug which is mounted in...

Page 10: ...le position in closed systems E A flow sensor ought not to be placed immediately after a valve with the exception of block valves ball valve type which must be fully open when not used for blocking F...

Page 11: ...Cutbush Park Danehill Lower Earley Reading Berkshire RG6 4UT UK Web able co uk E commerce 247able com 10 Kamstrup A S 55121739_A3_GB_04 2016 MULTICAL 403 3 3 Mounting of MULTICAL 403 flow sensor 90 9...

Page 12: ...eading Berkshire RG6 4UT UK Web able co uk E commerce 247able com 11 Kamstrup A S 55121739_A3_GB_04 2016 MULTICAL 403 3 4 Installation examples Threaded meter Flow from the left Flow from the right Fl...

Page 13: ...wall mounted Furthermore MULTICAL 403 in cooling applications must be the condensation proof version type 403 T The construction of MULTICAL 403 always provides minimum installation depth in connectio...

Page 14: ...s Controls Ltd Cutbush Park Danehill Lower Earley Reading Berkshire RG6 4UT UK Web able co uk E commerce 247able com 13 Kamstrup A S 55121739_A3_GB_04 2016 MULTICAL 403 4 3 Position of calculator If t...

Page 15: ...splayed in in TECH loop reading 2 017 00 for indication of current errors in MULTICAL 403 The info code consists of 8 digits and each functionality has its own digit dedicated to the indication of rel...

Page 16: ...ne D cell battery Optimal battery lifetime is obtained by keeping the battery temperature below 30 C e g by wall mounting The voltage of a lithium battery is almost constant throughout the lifetime of...

Page 17: ...on complies with current regulations The supply cable must not be protected by a fuse larger than the one permitted for the given cable size see examples below Supply cable Max Fuse 2 x 0 75 mm2 acces...

Page 18: ...nd valves to establish water flow through the system Activate the left front key primary key of MULTICAL 403 to change display reading and check that the displayed values for temperatures and water fl...

Page 19: ...for connection of extra meters with either Reed switch output or passive electronic pulse output Minimum pulse duration is 30 ms max pulse frequency is 3 Hz If a module with pulse inputs is mounted in...

Page 20: ...06 D SUB 9F or 66 99 098 USB type A with the following connections 62 Brown DAT 63 White REQ 64 Green GND 9 5 Data pulse outputs type HC 003 11 The data terminals are used for connection of e g a PC T...

Page 21: ...functionality The module is powered by the connected master 9 8 Wireless M Bus pulse inputs type HC 003 30 The wireless M Bus module has been designed to form part of Kamstrup s hand held Wireless M B...

Page 22: ...lude secondary readings and therefore the index number always consists of 4 digits In SETUP loop the right key secondary key is used for accessing individual readings with the purpose of changing para...

Page 23: ...e values Four minutes after the latest activation of any front key reading automatically changes to consumed energy Display readings Consumed energy in kWh MWh or GJ Activate to view yearly and monthl...

Reviews: